| 2001-01-08 00:00:00 | 1. SHEET A-1 NOTE #4 SHOWS TYPE VI CONST |
| | TYPE VI CONST. NOT ALLOWED IN FIRST FIRE |
| | DISTRICT SEE APPENDIX F, 1997 SBC. |
| | 2. REVISE SHEET A-1 TO REFLECT OPEANINGS |
| | SIZE ALLOWED BASED ON TYPE OF |
| | CONSTRUCTION USED SEE TABLE 600, 1997SBC |
| | 3.REVISE EXTERIOR WALL DESIGN FOR FIRE |
| | DISTRICT BASED ON FIRE DISTRICT AND |
| | TABLE 600, 1997 SBC. |
| | 4. SHEET A-2- INDICATES A DUCT BANK |
| | UNDER THE BUILDING NO EASEMENT RELEASES |
| | ON FILE. NO STRUCTURAL DETAILS ON PLANS. |
| | 5. SHEET A-20 CHANGE REFERENCE FROM PALM |
| | BEACH COUNTY TO THE CITY OF WEST PALM |
| | BEACH. |
| | 6. SUBMIT TRUSS DRAWINGS FOR REVIEW. |
| | 7. PROVIDE PRODUCT APPROVAL INFORMATION |
| | FOR WINDOWS AND DOORS AS PER REQUIREMENT |
| | SHEET A-33. |
| | 8. NOTE: CANOPIES, FENCES, GATES, SIGNS |
| | AND FOUNTIANS REQUIRE SEPERATE PERMITS. |
| | 9. SHEET A-28 MAILBOXES UNDER STAIRS |
| | COMPLY WITH 1006.1.4, 1997 SBC |
| | 10.SHEET A-29 SECTION A INDICATES WOOD |
| | FRAME ROOF SYSTEM ENERGY SHEET INDICATE |
| | CONCRETE ROOF WITH R10 INSULATION REVISE |
| | 11. SHEET A-32 INDICATES IN NOTES THAT |
| | MISSLE IMPACT NOTES ARE ON SHEET A-27. |
| | A-27 DOES NOT CONTAIN THE INFORMATION |
| | PROPER REFERENCE IS A-33. |
| | 12. SHEET A-32 DOOR SCHEDULE DOORS DO |
| | NOT MATCH ELEVATION SEE DOOR #7. |
| | 13. SHEET A-33 CODE REFERENCE FOR MISSLE |
| | IMPACT AND WIND DESIGN IS NOT CORRECT |
| | INDICATES 1994 SBC SHOULD BE 1997 SBC. |
| | 14. SHEET A-35 REFERENCES WRONG EDITION |
| | OF THE FAIR HOUSING ACT. |
| | 15. SHEET S-9 SECTION 7 INDICATES A |
| | 1 1/2" OFFSET, SHEET A-32 SECTION 5 |
| | INDICATES 1/2" AND COMPLIES WITH FAIR |
| | HOUSING ACT DOORS. |
| | 16. SHEET S-12 DOES NOT INDICATE CODE |
| | EDITION (1997) OR METHOUD OF COMPLIANCE |
| | 1606 OR ASCE-7-95 FOR BUILDING DESIGN. |