| Date |
Text |
| 2001-01-08 00:00:00 | 1. SHEET A-1 NOTE #4 SHOWS TYPE VI CONST |
| | TYPE VI CONST. NOT ALLOWED IN FIRST FIRE |
| | DISTRICT SEE APPENDIX F, 1997 SBC. |
| | 2. REVISE SHEET A-1 TO REFLECT OPEANINGS |
| | SIZE ALLOWED BASED ON TYPE OF |
| | CONSTRUCTION USED SEE TABLE 600, 1997SBC |
| | 3. REVISE EXTERIOR WALL DESIGN FOR FIRE |
| | DESTRICT BASED ON FIRE DESTRICT AND |
| | TABLE 600, 1997 SBC. |
| | 4. SHEET A-24 NOTES REFER TO SHEET A-27 |
| | SHEET NOT IN PLANS. |
| | 5. SUBMIT TRUSS DRAWINGS FOR REVIEW. |
| | 6. PROVIDE PRODUCT APPROVAL INFORMATION |
| | FOR WINDOWS AND DOORS AS PER SHEET A-33. |
| | 7. CANOPIES, FENCES, GATES, SIGNS AND |
| | FOUNTIANS REQUIRE SEPERATE PERMITS SEE |
| | SHEET A-41. |
| | 8. SHEET A-28 MAILBOXES UNDER STAIRS |
| | COMPLY WITH 1006.1.4, 1997 SBC. |
| | 9. SHEET A-29 SECTION A ETC. INDICATES |
| | WOOD FRAME ROOF SYSTEM ENERGY SHEET |
| | INDICATES CONCRETE ROOF WITH R10 |
| | INSULATION. |
| | 10. SHEET A-32 INDICATES IN NOTES THAT |
| | MISSLE IMPACT NOTES ARE ON SHEET A-27. |
| | A-27 DOES NOT CONTAIN THE INFORMATION |
| | PROPER REFRENCE IS A-33. |
| | 11. SHEET A-32 DOOR SCHEDULE DOORS DO |
| | NOT MATCH ELEVATIONS SEE DOOR #7. |
| | 12. SHEET A-33 CODE REFERENCE FOR MISSLE |
| | IMPACT AND WIND DESIGN IS NOT CORRECT |
| | PLAN INDICATES 1994 SBC SHOULD BE |
| | 1997 SBC. |
| | 13. SHEET A-35 REFERENCES THE WRONG |
| | EDITION OF THE FAIR HOUSING ACT. |
| | 14. SHEET S-9 SECTION 7 INDICATES A |
| | 1 1/2" OFFSET, SHEET A-32 SECTION 5 |
| | INDICATES 1/2" AND COMPLIES WITH FAIR |
| | HOUSING ACT. (DOORS) |
| | 15. SHEET S-12 DOES NOT INDICATE CODE |
| | EDITION (1997) OR METHOUD OF COMPLIANCE |
| | 1606 OR ASCE 7-95 FOR BUILDING DESIGN. |