| Plan Review Notes For Permit 99121189 |
| Permit Number |
99121189 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ****************DENIED****************** | | | | | | SBC 104.2.2 | | | | | | 1)PROVIDE OWNER SIGNATURE ON BOTH ENERGY | | | CALCULATIONS. | | | | | | 2)PROVIDE ENGINEER APPROVAL OF PILINGS | | | BEFORE ANY CONCRETE IS POURED. | | | | | | 3)PROVIDE FLOOD ZONE ELEVATION | | | CERTIFICATE. | | | | | | 4)PROVIDE AC PLAN WITH MECHANICAL PERMIT | | | APPLICATION. | | | | | | 5)PROVIDE 2 CURRENT COPIES OF SBCCI OR | | | METRO DADE PRODUCT APPROVALS WITH | | | APPROVED DRAWINGS FOR: | | | EXTERIOR DOORS AND WINDOWS | | | ROOF COVERING | | | STORM PANELS WITH INSTALLATION | | | SCHEDULE AND KEY PLAN WITH SPECIFIC | | | ANCHORS TO BE USED. | | | | | | 6)PROVIDE SPECIFICATIONS FOR UL LISTED | | | FIREPLACE. | | | | | | 7)PROVIDE DETAILS OF SPIRAL STAIRS TO | | | COMPLY WITH SBC 1007.8.2 | | | | | | 8)PROVIDE HANDRAILS AND GUARDRAILS TO | | | COMPLY WITH SBC 1015 | | | | | | 9)PROVIDE SAFETY GLASS PER SBC 2405.2.1 | | | | | | 10)PROVIDE DETAILS OF ALL STRUCTUAL | | | COMPONETS. MUST COMPLY WITH TBL 600, | | | TYPE VI 1 HR PROTECTED. | | | | | | 11)PROVIDE APPROVED ASSEMBLIES TO MEET | | | FIRE RESISTANCE REQUIREMENTS SBC 701.5 | | | | | | 11)SHOW FINISH FLOOR ELEVATIONS RELATIVE | | | TO NGVD. | | | | | | ******************NOTE****************** | | | ALL CHANGES ON PLANS MUST BE NOTED BY | | | TRIANGLES OR CLOUDS. |
|