 ****************DENIED******************
  
 SBC 104.2.2
  
 1)PROVIDE OWNER SIGNATURE ON ENERGY
 CALCULATIONS.
  
 2)PROVIDE ENGINEER APPROVAL OF PILINGS
 BEFORE ANY CONCRETE IS POURED.
  
 3)PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE.
  
 4)PROVIDE AC PLAN WITH MECHANICAL PERMIT
 APPLICATION.
  
 5)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR:
 EXTERIOR DOORS AND WINDOWS
 STORM PANELS
 ROOF COVERING
 FIREPLACE UL LISTED
  
 6)BUILDING SHOWN IS TYPE VI CONSTRUCTION
 AND DOES NOT COMPLY WITH SBC TABLE 500
 REVISE DESIGN TO COMPLY.
  
 7)PROVIDE CONSTRUCTION DETAILS OF FIRE
 RATED ASSEMBLY FOR ELEVATOR HOISTWAY
 SBC 705.1.2
  
 8)PROVIDE DETAILS OF SPIRAL STAIRS TO
 COMPLY WITH SBC 1007.8.2
  
 9)PROVIDE ATTIC ACCESS PER SBC 2309.6
  
 10)PROVIDE GUARDRAILS TO COMPLY WITH
 SBC 1015
  
 11)PROVIDE SAFETY GLASS PER SBC 2405.2.1
  
 12)PROVIDE CONSTRUCTION DETAILS OF FIRE
 RATED ASSEMBLY FOR LAUNDRY CHUTE
 SBC 705.1.2
  
 **************NOTE**********************
 BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECIEPT ATTACHED TO THE
 PERMIT APPLICATION.