2001-01-08 00:00:00SANITARY RISER SHALL CORRELATE W/FLOOR
 PLAN.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 MAIN VENT THRU ROOF REQD.PER SPC SEC.
 904.3.1.
  
 WATER CLOSETS AND FIXTURE BRANCHES NOT
 PERMITTED ON WET VENTS PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.911.1.1.
  
 FIXTURES DOWNSTREAM OF WATER CLOSETS
 SHALL BE VENTED PER SPC 913.2.