| 2001-01-08 00:00:00 | CHECKLIST: |
| | 1-PAY THE IMPACT FEES. |
| | 2-PROVIDE COMPLETE HANGING DETAILS FOR |
| | AHU SUSPENDED FROM FLOOR TRUSSES. |
| | 3-IN ORDER TO FACILITATE THE REVIEW |
| | PROCESS, PLEASE SPECIFY THE DESIRED |
| | OPTIONS FOR THIS HOUSE AND CROSS OUT |
| | THE OTHER OPTIONS. |
| | 4-FLOOD ZONE "A8" AN ELEVATION |
| | CERTIFICATE WILL BE REQUIRED. |
| | 5-EGRESS WINDOWS AT SECOND FLOOR TO |
| | COMPLY WITH THE MINIMUM REQUIREMENTS |
| | OF SECTION 1005.4.4 SBC 1997. REVISE |
| | SIZE OF WINDOWS AS REQUIRED. |
| | 6-PROVIDE ATTIC ACCESS AT GARAGE AREA. |
| | -REVISE SIZE OF ATTIC ACCESS SPECIFIED |
| | AT MASTER BEDROOM CLOSET. |
| | 7-PROVIDE FIRE CUTS AT TRUSSES TO BE |
| | SUPPORTED ON MASONRY WALL. SECTION |
| | 2305.4 SBC 1997 OR PROVIDE ANOTHER |
| | WAY TO COMPLY WITH THIS SECTION. |
| | NOTE: IF SOLUTION IS TO PROVIDE THE |
| | FIRE CUT, THEN FLOOR TRUSSES NEED TO |
| | BE REVISED ACCORDINGLY. |
| | 8-REVISE/UPDATE ALL DRAWINGS. SEE |
| | COMMENTS ON PLANS. |
| | 9-FOOTING F2 TO BE 16" |
| | SECTION 1804.1.3 SBC 1997. |
| | 10-PROVIDE PRODUCT APPROVAL FOR ENTRY |
| | DOOR WITH SIDELITES ASSEMBLY, GARAGE |
| | DOOR |
| | 11-STORM PANELS: |
| | -DRAWINGS DON'T MATCH PRODUCT APPROVAL. |
| | -UPDATE/REVISE INSTALLATION SCHEDULE |
| | AND KEY PLAN. USE CITY SAMPLE ATTACHED |
| | -SPECIFY ANCHOR SPACING AS REQUIRED |
| | FOR MASONRY AND WOOD CONSTRUCTION. |
| | 12-COMPLETELY SPECIFY CEILING |
| | CONSTRUCTION AT FRONT AND BACK PORCH. |
| | SECTION 104.2 CITY AMENDMENTS. |