| Plan Review Notes For Permit 99121095 |
| Permit Number |
99121095 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************UNSAT***************** | | | | | | 1)NOTE:PLEASE LABEL ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE GFI/GFI PROTECTED. | | | REQ`D BY 210-8-A-6 | | | | | | 2)NOTE:PLEASE SHOW MEANS OF DISC. FOR | | | A/C COND. UNIT. PER 440-11 | | | | | | 3)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE | | | AND OUTSIDE ALL SLEEPING ROOMS.IF ROOM | | | ON SECOND FLOOR HAS CLOSET INSTALLED | | | THEN A SMOKE DETECTOR WILL BE REQ`D. | | | THEY ARE REQ`D BY 1993/1996 NFPA-72 | | | 2-2.1.1.1 | | | | | | 4)NOTE: NEED TO SHOW DEDICATED BATH(S) | | | CIRCUT(S) ON PANEL SCHEDULE. THEY MUST | | | BE 20 AMP #12 AWG. THIS IS REQ`D BY | | | NEC.ART;210-52D/215-5 | | | | | | 5)NOTE: NEED TO SUBMIT AIC RATING OF | | | EQUIPMENT MAINS/PANEL. AIC RATING IS | | | FIGURED FROM FAULT CURRENT CALCULATIONS. | | | THIS IS REQ`D BY ARTS:110-9/230-65/215-5 | | | | | | 6)NOTE:PLEASE SIZE AND SHOW EQUIPMENT | | | GROUNDING CONDUCTOR AS REQ`D BY THE | | | FOLLOWING ARTS:250-92/250-95 AND 215-5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL BEFORE FIRST | | | ROUGH ELECTRICAL INSPECTION IS CALLED IN | | | IF THERE ARE ANY QUESTIONS,,PLEASE CALL | | | 659-8096 EXT 8372 |
|