Plan Review Notes
Plan Review Notes For Permit 99121095
Permit Number 99121095
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************UNSAT*****************
  
 1)NOTE:PLEASE LABEL ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE GFI/GFI PROTECTED.
 REQ`D BY 210-8-A-6
  
 2)NOTE:PLEASE SHOW MEANS OF DISC. FOR
 A/C COND. UNIT. PER 440-11
  
 3)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS.IF ROOM
 ON SECOND FLOOR HAS CLOSET INSTALLED
 THEN A SMOKE DETECTOR WILL BE REQ`D.
 THEY ARE REQ`D BY 1993/1996 NFPA-72
 2-2.1.1.1
  
 4)NOTE: NEED TO SHOW DEDICATED BATH(S)
 CIRCUT(S) ON PANEL SCHEDULE. THEY MUST
 BE 20 AMP #12 AWG. THIS IS REQ`D BY
 NEC.ART;210-52D/215-5
  
 5)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT MAINS/PANEL. AIC RATING IS
 FIGURED FROM FAULT CURRENT CALCULATIONS.
 THIS IS REQ`D BY ARTS:110-9/230-65/215-5
  
 6)NOTE:PLEASE SIZE AND SHOW EQUIPMENT
 GROUNDING CONDUCTOR AS REQ`D BY THE
 FOLLOWING ARTS:250-92/250-95 AND 215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL BEFORE FIRST
 ROUGH ELECTRICAL INSPECTION IS CALLED IN
 IF THERE ARE ANY QUESTIONS,,PLEASE CALL
 659-8096 EXT 8372