| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | | 1-FLOOD ZONE A8. PROVIDE ELEVATION | | | CERTIFICATE. | | | 2-UPDATE/REVISE ALL DRAWINGS AS REQUIRED | | | SEE PLANS FOR COMMENTS. | | | 3-ENGINEER TO SIGN, SEAL AND DATE SOIL | | | TEST REPORT. | | | 4-STORM PANELS: | | | -REVISE/UPDATE INSTALLATION SCHEDULE | | | AND KEY PLAN TO MATCH FLOOR PLANS. | | | NOTE: USE CITY SAMPLE INSTALLATION | | | SCHEDULE, ATTACHED, AND FILL IN ALL | | | THE INFORMATION. | | | 5-PROVIDE PRODUCT APPROVAL FOR ENTRY | | | OUTSWING DOOR AND GARAGE DOOR. | | | NOTE: CLEARLY SPECIFY THE FASTENERS | | | TO BE USED ACCORDING TO THE PRODUCT | | | APPROVAL AND DOOR FRAME DETAIL THAT | | | WAS SPECIFIED IN DRAWING A6. |
|