Plan Review Notes
Plan Review Notes For Permit 99121094
Permit Number 99121094
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************UNSAT*******************
  
 1)NOTE: RISER DIAGRAM SHOWS MAIN DISC.
 PLANS DO NOT SHOW MAIN DISCONNECT NEXT
 TO METER.?? PLEASE CORRECT.215-5
  
 2)NOTE:PANEL SCHEDULE SHOWS 48 CIRCUT
 PANELBOARD. AS PER 384-15 NO MORE THAN
 42 CIRCUT PANEL ARE ALLOWED.
  
 3)NOTE: AS PER 210-52D/215-5 NEED TO
 SHOW DEDICATED BATH(S) CIRCUT REQ`D.NEED
 TO BE 20AMP #12 AWG.
  
 4)NOTE;AS REQ`D BY 210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.PLEASE SHOW.
  
 5)NOTE:NEED TO SUBMIT AIC RATING OF
 EQUIPMENT MAINS/BRKRS. AS REQ`D BY THE
 FOLLOWING ARTS:110-9/230-65/215-5
 AIC RATING IS FIGURED FROM FAULT CURRENT
 CALCULATIONS.
  
 6)NOTE: AS REQ`D BY 1993/1996 NFPA-72
 CHAPTER 2-2.1.1.1 SMOKE DETECTORS SHALL
 BE INSTALLED INSIDE AND OUTSIDE ALL
 SLEEPING ROOMS IN NEW DWELLINGS.
  
 PLEASE HAVE ALL THE ABOVE INFORAMTION
 SUBMITTED FOR REVIEW AND APPROVAL
 BEFORE FIRST ROUGH ELECTRIACL INSPECTION
 IS CALLED IN. IF THERE ARE ANY QUESTIONS
 CALL 659-8096 EXT 8372