| Plan Review Notes For Permit 99121094 |
| Permit Number |
99121094 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************UNSAT******************* | | | | | | 1)NOTE: RISER DIAGRAM SHOWS MAIN DISC. | | | PLANS DO NOT SHOW MAIN DISCONNECT NEXT | | | TO METER.?? PLEASE CORRECT.215-5 | | | | | | 2)NOTE:PANEL SCHEDULE SHOWS 48 CIRCUT | | | PANELBOARD. AS PER 384-15 NO MORE THAN | | | 42 CIRCUT PANEL ARE ALLOWED. | | | | | | 3)NOTE: AS PER 210-52D/215-5 NEED TO | | | SHOW DEDICATED BATH(S) CIRCUT REQ`D.NEED | | | TO BE 20AMP #12 AWG. | | | | | | 4)NOTE;AS REQ`D BY 210-8-A-6 ALL OUTLETS | | | SERVING KITCHEN COUNTERSPACE ARE TO BE | | | GFI/GFI PROTECTED.PLEASE SHOW. | | | | | | 5)NOTE:NEED TO SUBMIT AIC RATING OF | | | EQUIPMENT MAINS/BRKRS. AS REQ`D BY THE | | | FOLLOWING ARTS:110-9/230-65/215-5 | | | AIC RATING IS FIGURED FROM FAULT CURRENT | | | CALCULATIONS. | | | | | | 6)NOTE: AS REQ`D BY 1993/1996 NFPA-72 | | | CHAPTER 2-2.1.1.1 SMOKE DETECTORS SHALL | | | BE INSTALLED INSIDE AND OUTSIDE ALL | | | SLEEPING ROOMS IN NEW DWELLINGS. | | | | | | PLEASE HAVE ALL THE ABOVE INFORAMTION | | | SUBMITTED FOR REVIEW AND APPROVAL | | | BEFORE FIRST ROUGH ELECTRIACL INSPECTION | | | IS CALLED IN. IF THERE ARE ANY QUESTIONS | | | CALL 659-8096 EXT 8372 |
|