| Plan Review Notes For Permit 99121043 |
| Permit Number |
99121043 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | | 1-SPECIFY CONNECTORS CAPABLE OF | | | RESISTING THE UPLIFT LOADS CALCULATED | | | ON THE ENGINEERED ROOF TRUSSES FOR THE | | | FOLLOWING TRUSSES: H6, H7, H8. | | | 2-REVISE ARCHITECT'S ROOF FRAMING PLAN | | | TO MATCH ROOF FRAMING PLAN SHOWN BY | | | THE TRUSS COMPANY. AND, SPECIFY THE | | | REQUIRED CONNECTORS. SEE COMMENTS ON | | | ROOF PLAN BY THE TRUSS COMPANY. |
|