| Plan Review Notes For Permit 99120815 |
| Permit Number |
99120815 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | REQD.NUMBER OF PLUMBING FIXTURES PER SQ. | | | FOOTAGE OF BUILDING SHALL COMPLY W/SPC | | | SEC.407.1.3.(THE CORE RESTROOMS DO NOT | | | CONTAIN THE CORRECT NUMBER OF PLBG. | | | FIXTURES.) | | | | | | SUBMIT STORM DRAINAGE RISER DIAGRAM FOR | | | REVIEW.SHOW SQ.FOOTAGE OF ROOF AREA | | | DRAINED BY EACH DRAIN AND INCLUDE 1/2 | | | AREA OF VERTICAL WALL INTO DESIGN CALCS. | | | PER SPC SEC.1108.3. | | | | | | CLEARLY SHOW DISCHARGE PT.OF OVERFLOW | | | DRAINS.COMPLY W/SPC 301.2. | | | | | | | | | SHT.PO.1-"M" COPPER NOT PERMITTED U/G | | | COUNTYWIDE AMENDMENTS TO SPC SEC.611.3. | | | | | | A BACKFLOW PREVENTION DEVICE IS REQD. | | | ON SUPPLY TO FOUNTAIN PER SPC SEC.606.1, | | | 606.2. | | | | | | A WATER PERMIT MAY BE REQD.FOR THE WATER | | | SERVICE.CONTACT PALM BCH.COUNTY HEALTH | | | DEPT.AND FLA.DEPT.OF ENVIRON.PROTECTION. | | | PROOF OF REVIEW BY THESE DEPTS.SHALL BE | | | SUBMITTED .COUNTYWIDE AMENDMENTS TO SPC | | | SEC.101.4.7. | | | | | | INDICATE WATER SOURCE FOR IRRIG.SYSTEM. | | | A WATER USE PERMIT MAY BE REQD.PER F.S. | | | 373.219. |
|