Plan Review Notes
Plan Review Notes For Permit 99120815
Permit Number 99120815
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00REQD.NUMBER OF PLUMBING FIXTURES PER SQ.
 FOOTAGE OF BUILDING SHALL COMPLY W/SPC
 SEC.407.1.3.(THE CORE RESTROOMS DO NOT
 CONTAIN THE CORRECT NUMBER OF PLBG.
 FIXTURES.)
  
 SUBMIT STORM DRAINAGE RISER DIAGRAM FOR
 REVIEW.SHOW SQ.FOOTAGE OF ROOF AREA
 DRAINED BY EACH DRAIN AND INCLUDE 1/2
 AREA OF VERTICAL WALL INTO DESIGN CALCS.
 PER SPC SEC.1108.3.
  
 CLEARLY SHOW DISCHARGE PT.OF OVERFLOW
 DRAINS.COMPLY W/SPC 301.2.
  
  
 SHT.PO.1-"M" COPPER NOT PERMITTED U/G
 COUNTYWIDE AMENDMENTS TO SPC SEC.611.3.
  
 A BACKFLOW PREVENTION DEVICE IS REQD.
 ON SUPPLY TO FOUNTAIN PER SPC SEC.606.1,
 606.2.
  
 A WATER PERMIT MAY BE REQD.FOR THE WATER
 SERVICE.CONTACT PALM BCH.COUNTY HEALTH
 DEPT.AND FLA.DEPT.OF ENVIRON.PROTECTION.
 PROOF OF REVIEW BY THESE DEPTS.SHALL BE
 SUBMITTED .COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.4.7.
  
 INDICATE WATER SOURCE FOR IRRIG.SYSTEM.
 A WATER USE PERMIT MAY BE REQD.PER F.S.
 373.219.