Plan Review Notes
Plan Review Notes For Permit 99120778
Permit Number 99120778
Review Stop M
Sequence Number 1
Notes
Date Text
2001-02-12 00:00:00PROVISO:CONDENSER UNIT STAND SHALL BE
 A MINIMUM OF 18" FROM TOP OF ROOF TO
 BOTTOM SUPPORT OF THE STAND.
  
 AS PER 1997 SMC 406.1 - RTU-1SHALL
 HAVE FAN SHUT BY MEANS OF AN APPROVED
 SMOKE DETECTOR PLACED IN RETURN AIR,
 PRIOR TO ANY EXHAUSTING FROM THE
 BUILDING OR MIXING WITH ANY FRESH AIR
 MAKE-UP.