| 2001-01-08 00:00:00 | CONTINUATION OF PLBG.COMMENTS: |
| | |
| | SHT.P-13-FLOOR DRAINS NOT PROPERLY |
| | VENTED.SPC SEC.901.2. |
| | |
| | SHT.P-16-JOINTS ON WATER DISTRIBUTION |
| | SYSTEM NOT PERMITTED UNDER SLAB INSIDE |
| | BUILDING PER COUNTYWIDE AMENDMENTS SEC. |
| | 611.3.SEE DETAIL #4. |
| | |
| | FIXTURES HAVING SLIP JOINT CONNECTIONS |
| | SHALL COMPLY W/SPC SEC.401.5.2.(SEE |
| | SHT.P-16,DETAIL #1. |
| | |
| | MINIMUM SIZE OF DRAINAGE PIPE UNDER- |
| | GROUND SHALL BE 2" PER SPC SEC.714.4. |
| | |
| | BACKWATER VALVES SHALL BE INSTALLED ON |
| | DRAIN CONNECTIONS FROM FOUNTAINS TO |
| | STORM SYSTEM PER SPC 301.11.1,409.9.2. |
| | |
| | SHTS.A1.32-ROOM#1627 & A1.34 &1.36-ROOM |
| | #1647-SHOWERS SHALL COMPLY W/FACBC SECS. |
| | 4.21.2-4.21.8.WASHER AND DRYER SHALL |
| | COMPLY W/FACBC SEC.6.1(1). |
| | |
| | VOID ALL PREVIOUS PLBG.SHEETS REPLACED |
| | BY NEW REVISIONS AND INSERT NEW SHEETS |
| | INTO PLANS .COUNTYWIDE AMENDMENTS TO SPC |
| | SEC.104.2.1. |
| | |
| | SHT.P24-VENT SIZING SHALL COMPLY W/SPC |
| | TABLE 920.2,920.4. |
| | |
| | SHT.P24-THE SANITARY SCHEMATIC IS VAGUE |
| | REGARDING THE LINE SIZES FOR THE DRAIN- |
| | AGE SYSTEM.THERE ARE SECTIONS WITH NO |
| | SIZES,LONG RUNS W/NO SIZES, |
| | |
| | SHT.P24-HORIZONTAL DRAIN PIPING LACKS |
| | SIZES AND SCHEMATIC DOESN'T REFLECT |
| | THE SYSTEM AS DRAWN ON SHTS.P3 & P4. |
| | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 |
| | |
| | VENTS NOT PERMITTED TO INCREASE IN SIZE. |
| | SPC 905.2.(PERMITTED ONLY WHERE FROST |
| | CLOSURE IS A PROBLEM.) |
| | |
| | NOTE:I RECOMMEND A MEETING W/THE DESIGN |
| | PROFESSIONALS AND MYSELF TO CLARIFY |
| | ISSUES,EPECIALLY THE PLUMBING SCHEMATIC. |
| | |
| | PLEASE CALL 561-659-8096 EXT.8377 IF YOU |
| | HAVE ANY QUESTIONS. |
| | TIMOTHY K.LARGE,PLUMBING PLAN REVIEW. |