| Date |
Text |
| 2001-01-08 00:00:00 | SUBMIT COPY OF JOB SPECIFICATIONS AND |
| | COMPLETE PLUMBING DRAWINGS INCUDING |
| | ISOMETRICS FOR STORM,SANITARY,WATER AND |
| | ALL OTHER RELATED PLUMBING SYSTEMS PER |
| | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 |
| | |
| | SUBMIT OCCUPANT LOAD PER SPC SEC.407.1.3 |
| | TO ENSURE COMPLIANCE FOR MINIMUM REQD. |
| | SANITARY FACILITIES. |
| | |
| | SHT.C1.00-SHOW SQ.FT.AREA DRAINED BY |
| | EACH AREA DRAIN.COMPLY W/SPC TABLE |
| | 1108.2. |
| | |
| | SHT.C2.00-LOCATION OF BFP DEVICE SHALL |
| | BE APPROVED BY CITY OF WPB UTILITIES. |
| | CALL 659-8000,EXT.2008. |
| | |
| | SHT.AO-11-SUBMIT DETAILS FOR RIVER ROCK |
| | FOUNTAIN.(FILL LINE,DRAINS,PUMP,ETC)PER |
| | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 |
| | |
| | SHT.A1-1-REVISE PLBG.STANDARD AT CODE |
| | BRIEF TO READ 1994 ED.PER COUNTYWIDE |
| | AMENDMENTS TO SPC SEC.101.1,101.2. |
| | |
| | FLOORS AND WALLS IN TOILET ROOMS/REST- |
| | ROMMS SHALL BE NONABSORBENT TO A HEIGHT |
| | OF 4' PER SBC SEC.1204.2. |
| | |
| | FLOOR DRAINS ARE REQD.IN ALL TOILET/ |
| | RESTROOMS PER SPC SEC.409.4.1.1(SEE |
| | EXCEPTION). |
| | |
| | SUBMIT DETAILS FOR OVERFLOW DRAINAGE FOR |
| | ROOF STRUCTURE.COMPLY W/SBC 1517.6.4.1, |
| | THRU 1517.6.4.3.,1109.1- 1109.3.,AND |
| | APPENDIX "A"OF SPC. |
| | |
| | CLEARLY SHOW ALL RESTROOM/TOILET ROOM & |
| | TOILET STALL DIMENSIONS ON ARCH.FLOOR |
| | PLANS.COUNTYWIDE AMENDMENTS TO SPC SEC. |
| | 104.2.1,104.2.2. |
| | |
| | ALL HANDICAP TOILET STALLS SHALL CONTAIN |
| | AN ACCESSIBLE LAVATORY WITHIN THE STALL |
| | PER FACBC SEC.4.17.3(EXCEPTION:NEW |
| | CONSTRUCTION). |
| | |
| | ALL LOUNGE/BREAKROOM SINKS AND SINKS |
| | LOCATED IN OTHER NON-WORK AREAS SHALL |
| | BE FULLY ACCESSIBLE AND COMPLY W/FACBC |
| | SEC.4.24.1-4.24.7. |
| | |
| | CLEARLY SHOW DIMENSIONS (LXW)OF ALL |
| | SHOWER STALLS.SIZE OF ACCESSIBLE SHOWERS |
| | SHALL COMPLY W/FACBC SECS.4.21-4.21.8. |
| | OTHER SHOWERS SHALL BE ADAPTABLE PER |
| | FACBC SEC.4.1.3.(11).SEAT IN SHOWER |
| | SHALL COMPLY W/FACBC SEC.4.21.3. |
| | |
| | URINALS SHALL COMPLY W/FACBC SEC.4.18.1- |
| | 4.18.4. |
| | |
| | FLUSH CONTROLS FOR WATER CLOSETS SHALL |
| | COMPLY W/FACBC SEC.4.16.5. |
| | |
| | DRINKING FOUNTAINS ARE REQD.PER SPC |
| | TABLE 407 AND ACCESSIBLE FOUNTAINS SHALL |
| | COMPLY W/FACBC SEC.4.1.3.(10)(A)(B). |
| | |
| | ACCESSIBLE WATER CLOSETS IN STALLS SHALL |
| | BE LOCATED IN THE CORNER,DIAGONAL TO THE |
| | DOOR PER FACBC SEC.4.17.3(EXCEPTION:NEW |
| | CONSTRUCTION). |
| | |
| | MEDICAL CARE FACILITIES SHALL COMPLY W/ |
| | FACBC SECS.6.1(1).(10% RULE) AND 6.1(4) |
| | (A)(B),6.4. |
| | |
| | BATHTUBS IN ACCESSIBLE PATIENT ROOMS |
| | SHALL COMPLY W/FACBC SEC.4.20.1-4.20.7. |
| | |
| | CLEARLY SHOW WHEELCHAIR TURNING SPACE IN |
| | ACCESSIBLE TOILET ROOMS AND STALLS PER |
| | FACBC SEC.4.2.3. |
| | |
| | SHT.A6-2-SUBMIT U.L.ASSEMBLY NUMBERS FOR |
| | FIRE SAFING DETAILS PER SBC 701.5.2. |
| | (1996 ED.)AND SBC SEC.3502. |
| | |
| | SUBMIT COMPLETE INFO FOR SECONDARY ROOF |
| | DRAINAGE |
| | |
| | PLUMBING INSTALLATION SHALL COMPLY W/SPC |
| | APPENDIX "G"FOR HOSPITALS. |
| | |
| | MUTIPLE/GANG SHOWERS SHALL COMPLY W/SPC |
| | SEC.409.8.3. |
| | *****(SEE PLBG.STEP#2FOR CONTINUATION)** |