| 2001-01-08 00:00:00 | PASSED WITH PROVISOS: |
| | |
| | STORMWATER COMMENTS: |
| | |
| | 1.THE ENGINEER OF RECORD SHOULD PUT |
| | TOGETHER A LIST OF EXISTING IMPERVIOUS |
| | AND PERVIOUS AREAS AS WELL AS A LIST OF |
| | NEW IMPERVIOUS AND IMPERVIOUS ARES, TO |
| | SHOW WHAT THE NEW ERU RATE WILL BE. |
| | PLEASE SUBMIT PLANS SHOWING PRIOR TO |
| | DEMOLITION AND FINAL DESIGN SO WE CAN |
| | COMPARE THE TWO. |
| | |
| | 4.THE STORMWATER SYSTEM ON THE HOSPITAL |
| | PROPERTY IS ALL PRIVATE AND AS SUCH WE |
| | HAVE NO COMMENTS ABOUT THE DESIGN, |
| | EXCEPT WHAT IS WRITTEN ABOVE. |
| | |
| | WATER AND SANITARY: |
| | |
| | 1.ALL ON SITE PIPING IS A PRIVATE |
| | DISTRIBUTION SYSTEM METERED AND |
| | PROTECTED WITH BACKFLOW PREVENTERS AT |
| | 45TH AND GREENWOOD AVENUES. ALL OF THE |
| | GRAVITY SYSTEM FROM 45TH STREET NORTH |
| | AND GREENWOOD WEST IS PRIVATE OWNED BY |
| | ST. MARY'S.AS SUCH WE DO NOT NEED TO |
| | REVIEW THIS DESIGN FOR COMPLIANCE TO OUR |
| | STANDARDS. BUT I MAKE THE FOLLOWING |
| | COMMENTS FOR ITEMS THAT I SEE AS |
| | POSSIBLY INCORRECT: |
| | |
| | 2.A 4" METER IS SHOWN AT THE NORTHWEST |
| | CORNER OF THE BUILDING, IT IS NOT |
| | REQUIRED BY THE PUBLIC UTILITY |
| | DEPARTMENT SINCE WE MASTER METER THE |
| | SITE. |
| | |
| | 3.SINCE ALL OF THE SANITARY SEWER SYSTEM |
| | IS A PRIVATE, ONE OWNER SYSTEM, A DEP |
| | PERMIT MAY NOT BE REQUIRED.CONTACT |
| | JAMES L. (DUTCH) HOLLAND, ENVIRONMENTAL |
| | ENGINEER (PLAN REVIEWER), AT |
| | W-561:355-4045, EX. 1134F-561:355-2442 |
| | AND DISCUSS IT WITH HIM OR ONE OF THE |
| | OTHER PLAN REVIEWERS. |
| | |
| | 4.THE FIRE LINE THAT COME OFF OF THE |
| | MASTER METERED DOMESTIC DISTRIBUTION |
| | MAIN DOES NOT APPEAR TO HAVE AN APPROVED |
| | DOUBLE CHECK BACKFLOW PREVENTER ON IT, |
| | IT SHOULD HAVE ONE TO STOP ANY WATER |
| | FROM COMING INTO THE SYSTEM WHEN PUMPED |
| | INTO THE FDC.PLEASE CHECK AND SEE IF |
| | EXISTS AND WAS LEFT OFF THE PLAN BY |
| | MISTAKE OR IF IT NEEDS TO BE ADDED. |
| | |
| | 5.THE REDUCED PRESSURE BACKFLOW |
| | PREVENTER SHOWN IS A SINGLE DEVICE.WE |
| | STRONGLY SUGGEST ON DOMESTIC, CRITICAL |
| | USAGE LOCATIONS, SUCH AS THIS THAT TWO |
| | DEVICES ARE INSTALLED IN PARALLEL.THIS |
| | WAY IF ONE FAILS OR HAS TO BE SHUT OFF |
| | TO BE WORKED ON THE HOSPITAL IS NOT |
| | WITHOUT WATER. |
| | |
| | 6.THE TEMPORARY JUMPER CONNECTION SHOWN |
| | ON PAGE C3.01 IS WRONG.TWO IN-LINE |
| | VALVES ARE REQUIRED WITH AN OPEN VENT |
| | BETWEEN.THIS ALLOWS WATER TO PASS THRU |
| | THE PROTECTED BYPASS FOR TESTING AND |
| | WITHOUT THE CHANCE OF BACKFLOW THRU THE |
| | SINGLE VALVE.THIS IS A DEP REQUIREMENT |
| | ALSO. |