Date Text
2001-01-08 00:00:00***************PROVISO******************
  
 1)NOTE:AS PER 250-81/215-5 NEED TO SHOW
 BLDG.STEEL AS PART OF THE GROUNDING
 ELECTRODE SYSTEM.
  
 2)NOTE:AS PER 210-52D/215-5 NEED TO HAVE
 DEDICATED BATH(S) CIRCUT(S) 20 AMP#12
 AWG DRAWN ON PANEL SCHEDULE.
  
 3)NOTE: NEED TO SUBMIT AIC RATING OF
 PANEL/BKRS. AIC RATING IS FIGURED FROM
 FAULT CURRENT CALCULATIONS.
  
 4)NOTE:MISSING WP GFI OUTLETS REQ`D
 FRONT AND BACK OF DWELLINGS AS PER ART:
 210-52E
  
 5)NOTE:MISSING OUTLETS REQ`D AS PER ART:
 210-52 MASTER BR/AND BR#3 2`OF WALL.
  
 6)NOTE:MISSING WP GFI REQ`D FOR A/C
 AS PER 210-63
  
 7)NOTE: AS REQ`D PER 1993/1996 NFPA-72
 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 IN NEW DWELLINGS.
  
 8)NOTE: OUTLET SPACING IN KITCHEN IS TO
 MEET REQ`MENTS PER 210-52-C-1. 12"OF
 COUNTER SPACE.
  
 9)NOTE:OUTLET REQ`D FOR PENINSULAR PER
 210-52-C-3
  
 10)NOTE: ALL OUTLETS IN KITCHEN SERVING
 COUNTERSPACE ARE REQ`D TO BE GFI/GFI
 PROTECTED. AS PER 210-8-A-6
  
 ALL THE ABOVE NEEDS TO BE SUBMITTED FOR
 REVIEW AND APPROVAL BEFORE FIRST ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.
 IF THERE ARE ANY QUESTIONS;PLEASE CALL
 659-8096 EXT 8372