| Plan Review Notes For Permit 99120507 |
| Permit Number |
99120507 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************PROVISO******************* | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATING OF | | | EQUIPMENT MAINS AND BRKRS. AIC RATING IS | | | FIGURED FROM FAULT CURRENT CALCULATIONS. | | | REQ`D PER 230-65/110-9/215-5. | | | | | | 2)NOTE: PLEASE SHOW BLDG. STEEL AS PART | | | OF THE GROUNDING SYSTEM PER 250-81/215-5 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | | BEFORE ROUGH ELECTRICAL INSPECTION IS | | | CALLED IN. IF THERE ARE ANY QUESTIONS | | | CALL 659-8096 EXT 8372 |
|