| 2001-01-08 00:00:00 | ******************PROVISO*************** | | | | | | FLOOR DRAIN NOT PERMITTED IN ROOM W/AIR | | | HANDLER IF ROOM IS USED AS PLENUM.SPC | | | SEC.409.4.4.1 | | | | | | HEAT TRAPS REQD.ON EWH PER FEC SEC. | | | 412.1ABCD.2.1.3. | | | | | | WATER HEATER SHALL BE READILY ACCESSIBLE | | | PER SPC SEC.501.7.SUPPLY PERMANENT | | | LADDER AND PLATFORM OR RELOCATE TO FLOOR |
|