| 2001-01-08 00:00:00 | **********PROVISO*********************** | | | | | | 1)PROVIDE EXHAUST FROM JANITORS CLOSET | | | PER 1997 SMC 503.2 | | | 2) EXHAUST DUCT (8") PENETRATING DEMIS- | | | ING WALL TO BE PROTECTED BY FIRE DAMPERS | | | OR COMPLY W/ EXCEPTIONS AND NOTES 1997 | | | SMC 610.1.3(3)1,2,3, AND 4 | | | 3)DUCT SMOKE DETECTORS TO BE TIED TO | | | BLDG FIRE ALARM FOR NOTIFICATION PER | | | NFPA 90A 4-4.4.2 |
|