| 2001-01-08 00:00:00 | JOB SPEC.02700-6-SEC.2.11-MATERIALS |
| | SHALL COMPLY W/STANDARDS REFERENCED IN |
| | SPC SEC.1402.(SEE ASTM C 478). |
| | |
| | JOB SPEC.15440-1-SEC.1.03-FIXTURES SHALL |
| | COMPLY W/ SEC.406 OF SPC(WATER SAVING). |
| | SCHEDULE ON P-1 DOESN'T SPECIFY. |
| | |
| | INDICATE WATER SOURCE FOR IRRIGATION |
| | SYSTEM.IF FROM AN ARTIFICIAL BODY OF |
| | WATER OR WELL,A WATER USE PERMIT FROM |
| | SFWMD SHALL BE REQUIRED PER F.S.373.219. |
| | |
| | A RAIN SENSOR IS REQUIRED ON THE |
| | IRRIGATION SYSTEM PER F.S.373.62. |
| | |
| | SINK IN KITCHEN AND COMMON AREA SHALL |
| | COMPLY W/FACBC SECS.4.24.1-4.24.7. |
| | |
| | SUBMIT INFORMATION ON THE TYPE OF |
| | MATERIALS BEING STORED IN THE WAREHOUSE. |
| | AN EMERGENCY SHOWER MAY BE REQD. PER |
| | TABLE 407. |
| | |
| | SUBMIT OCCUPANT LOAD ON THE PLANS. |
| | DOCUMENTATION SHALL BE SUBMITTED BY |
| | OWNER AS PER OCCUPANT CONTENT PER SHIFT |
| | PER TABLE 407 OF SPC. |
| | |
| | WATER SUPPLY CONTROL SHALL COMPLY W/SPC |
| | SEC.610.4.1,610.4.2. |
| | |
| | VENTS THRU ROOF SHALL NOT BE INCREASED |
| | IN SIZE PER SPC SEC.905.2.(APPROVED ONLY |
| | WHERE FROST IS A PROBLEM.) |
| | |
| | SUBMIT ELEVATION DETAIL OF DRINKING |
| | FOUNTAIN.COMPLY W/FACBC SEC.4.15 AND |
| | FIGURE 27. |