2001-01-08 00:00:00SHOW LOCATION OF ROOF DRAINS ON ARCH.
 PLAN AND SUBMIT STORM DRAINAGE ISOMETRIC
 FOR REVIEW.SHOW SQ.FOOTAGE DRAINED BY
 EACH DRAIN.COMPLY W/SB SEC.1517.6.4.1.,
 1517.6.4.2.,1517.6.4.3.,TABLE 1108.1,
 1108.2.
  
 PROVIDE DETAILS FOR SECONDARY DRAINAGE.
 COMPLY W/SPC SEC.1109.2,1109.3,AND
 APPENDIX "A",SEC.A101.2 AND TABLE A101.2
  
 FLUSH CONTROLS FOR HANDICAP WATER CLOSET
 SHALL BE LOCATED ON WIDE SIDE PER FACBC
 SEC.4.16.5.
  
 FLOOR DRAIN NOT PERMITTED IN MECHANICAL
 ROOM W/AIR HANDLER WHEN ROOM IS USED AS
 PLENUM PER SPC SEC.409.4.4.1.