| Plan Review Notes For Permit 99120159 |
| Permit Number |
99120159 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SHOW LOCATION OF ROOF DRAINS ON ARCH. | | | PLAN AND SUBMIT STORM DRAINAGE ISOMETRIC | | | FOR REVIEW.SHOW SQ.FOOTAGE DRAINED BY | | | EACH DRAIN.COMPLY W/SB SEC.1517.6.4.1., | | | 1517.6.4.2.,1517.6.4.3.,TABLE 1108.1, | | | 1108.2. | | | | | | PROVIDE DETAILS FOR SECONDARY DRAINAGE. | | | COMPLY W/SPC SEC.1109.2,1109.3,AND | | | APPENDIX "A",SEC.A101.2 AND TABLE A101.2 | | | | | | FLUSH CONTROLS FOR HANDICAP WATER CLOSET | | | SHALL BE LOCATED ON WIDE SIDE PER FACBC | | | SEC.4.16.5. | | | | | | FLOOR DRAIN NOT PERMITTED IN MECHANICAL | | | ROOM W/AIR HANDLER WHEN ROOM IS USED AS | | | PLENUM PER SPC SEC.409.4.4.1. |
|