Plan Review Notes
Plan Review Notes For Permit 99120159
Permit Number 99120159
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00JOB SPEC.02700-6-SEC.2.09(B)-MATERIALS
 SHALL COMPLY W/STANDARDS REFERENCED IN
 SPC SEC.1402.
  
 JOB SPEC.02700-7-SEC.2.10-DELETE "CITY
 OF BOCA RATON"FROM SPEC.COMPLY W/CITY OF
 WEST PALM BEACH REQS.
  
 JOB SPEC.02700-7-SEC.2.11-MANHOLES TO
 COMPLY W/SEC.1402 OF SPC.
  
 JOB SPEC.15408-1-SEC.1.03-INSERT 1994
 EDITION OF STANDARD PLUMBING CODE PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.100.
  
 JOB SPEC.15408-2-SEC.1.03(A)-SLOPE OF
 SANITARY DRAINAGE PIPE SHALL COMPLY W/
 SPC SEC.705.
  
 JOB SPEC.15440-1-SEC.1.03-FIXTURES SHALL
 COMPLY W/SEC.406 OF SPC.(WATER SAVING).
  
 JOB SPEC.15992-3-SEC.1.06,1.07-TESTING
 OF SANITARY AND WATER SYSTEMS SHALL
 COMPLY W/SPC SECS.311.1.2.1,311.3
  
 INDICATE OCCUPANT LOAD FOR COMPLIANCE
 W/TABLE 407 OF SPC.
  
 INDICATE WATER SUPPLY SOURCE FOR IRRIG.
 SYSTEM.IF FROM AN ARTIFICIAL BODY OF
 WATER OR WELL A WATER USE PERMIT FROM
 SFWMD SHALL BE REQD.PER F.S.373.219.
  
 A RAIN SENSOR IS REQD.ON THE IRRIGATION
 SYSTEM PER F.S.373.62.
  
 KIT.SINK SHALL COMPLY W/FACBC SEC.4.24.1
 THRU 4.24.7.
  
 HANDICAP STALLS SHALL COMPLY W/FACBC
 SEC.4.17.3.(A LAVATORY IS REQD.WITHIN
 THE STALL-SEE EXCEPTION:NEW CONSTRUCTION
  
 DRINKING FOUNTAINS SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS REQD.FOR
 PERSONS HAVING TROUBLE BENDING OR STOOP-
 ING.
  
 SIZE OF HANDICAP STALLS SHALL COMPLY W/
 FACBC SEC.4.17.3 AND FIGURE 28.
  
 URINAL SHALL BE SET AT HANDICAP HEIGHT.
 COMPLY W/FACBC SEC.4.18 FOR REQS.AND
 CLEAR FLOOR SPACE.
  
 SHT.7A-4-HEIGHT OF W.C.'S SHALL COMPLY
 W/FACBC SEC.4.16.3.AND FIGURE 28.(SPACE
 FROM FINISH WALL).
  
 EMERG.SHOWER REQD.IN WAREHOUSE PER SPC
 TABLE 407.(SEE FOOTNOTE #14 ALSO.)
  
 SHT.7-S7-PLAN SHOWS PVC DRAINS BY DIS-
 PENSERS.SHOW TERMINATION POINT.AN INTER-
 CEPTOR MAY BE REQD.SPC SEC.1004.1.
  
 SHT.7-P1-WATER HEATER SHALL BE READILY
 ACCESSIBLE PER SPC SEC.501.7.SUPPLY A
 FIXED LADDER OR RELOCATE WATER HEATER TO
 FLOOR.
  
 RELIEF DRAIN AND PAN DRAIN SHALL NOT USE
 COMMON RISER PER COUNTYWIDE AMENDMENT TO
 SPC SEC.507.8.3.,507.8.4.
  
 SHT.7P-2-NOTE #3-FLOOR SINK OR FLOOR
 DRAIN SHALL BE INSTALLED IN LIEU OF HUB
 DRAIN.
  
 SHT.7P-2-NOTE#6-BACKWATER VALVE SHALL BE
 ACCESSIBLE PER SPC SEC.1112.5.
  
 SHT.7P-2-DETAIL #6-VENTS THRU ROOF SHALL
 NOT INCREASE IN SIZE PER SPC 905.2,918.
 SEE 7P-3-DETAIL#4 ALSO.
  
 SHT.7P-2-DETAILS#3 & #5-WATER SUPPLY
 SHALL COMPLY W/SPC SECS.610.4.1.&
 610.4.2.
  
 SHT.7P-3-WATER CLOSETS AND FIXTURE
 BRANCHES NOT PERMITTED ON WET VENT PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.911.1.1
  
 VENTING SYSTEM SHALL BE SIZED PER SPC
 TABLE 920.2.9 SEE AREA AT BACK TO BACK
 WATER CLOSETS.
  
 COMMENTS CONTINUED ON SECOND PLBG.STEP.