| 2001-01-08 00:00:00 | JOB SPEC.02700-6-SEC.2.09(B)-MATERIALS |
| | SHALL COMPLY W/STANDARDS REFERENCED IN |
| | SPC SEC.1402. |
| | |
| | JOB SPEC.02700-7-SEC.2.10-DELETE "CITY |
| | OF BOCA RATON"FROM SPEC.COMPLY W/CITY OF |
| | WEST PALM BEACH REQS. |
| | |
| | JOB SPEC.02700-7-SEC.2.11-MANHOLES TO |
| | COMPLY W/SEC.1402 OF SPC. |
| | |
| | JOB SPEC.15408-1-SEC.1.03-INSERT 1994 |
| | EDITION OF STANDARD PLUMBING CODE PER |
| | COUNTYWIDE AMENDMENTS TO SPC SEC.100. |
| | |
| | JOB SPEC.15408-2-SEC.1.03(A)-SLOPE OF |
| | SANITARY DRAINAGE PIPE SHALL COMPLY W/ |
| | SPC SEC.705. |
| | |
| | JOB SPEC.15440-1-SEC.1.03-FIXTURES SHALL |
| | COMPLY W/SEC.406 OF SPC.(WATER SAVING). |
| | |
| | JOB SPEC.15992-3-SEC.1.06,1.07-TESTING |
| | OF SANITARY AND WATER SYSTEMS SHALL |
| | COMPLY W/SPC SECS.311.1.2.1,311.3 |
| | |
| | INDICATE OCCUPANT LOAD FOR COMPLIANCE |
| | W/TABLE 407 OF SPC. |
| | |
| | INDICATE WATER SUPPLY SOURCE FOR IRRIG. |
| | SYSTEM.IF FROM AN ARTIFICIAL BODY OF |
| | WATER OR WELL A WATER USE PERMIT FROM |
| | SFWMD SHALL BE REQD.PER F.S.373.219. |
| | |
| | A RAIN SENSOR IS REQD.ON THE IRRIGATION |
| | SYSTEM PER F.S.373.62. |
| | |
| | KIT.SINK SHALL COMPLY W/FACBC SEC.4.24.1 |
| | THRU 4.24.7. |
| | |
| | HANDICAP STALLS SHALL COMPLY W/FACBC |
| | SEC.4.17.3.(A LAVATORY IS REQD.WITHIN |
| | THE STALL-SEE EXCEPTION:NEW CONSTRUCTION |
| | |
| | DRINKING FOUNTAINS SHALL COMPLY W/FACBC |
| | SEC.4.1.3.(10)(A).PROVISIONS REQD.FOR |
| | PERSONS HAVING TROUBLE BENDING OR STOOP- |
| | ING. |
| | |
| | SIZE OF HANDICAP STALLS SHALL COMPLY W/ |
| | FACBC SEC.4.17.3 AND FIGURE 28. |
| | |
| | URINAL SHALL BE SET AT HANDICAP HEIGHT. |
| | COMPLY W/FACBC SEC.4.18 FOR REQS.AND |
| | CLEAR FLOOR SPACE. |
| | |
| | SHT.7A-4-HEIGHT OF W.C.'S SHALL COMPLY |
| | W/FACBC SEC.4.16.3.AND FIGURE 28.(SPACE |
| | FROM FINISH WALL). |
| | |
| | EMERG.SHOWER REQD.IN WAREHOUSE PER SPC |
| | TABLE 407.(SEE FOOTNOTE #14 ALSO.) |
| | |
| | SHT.7-S7-PLAN SHOWS PVC DRAINS BY DIS- |
| | PENSERS.SHOW TERMINATION POINT.AN INTER- |
| | CEPTOR MAY BE REQD.SPC SEC.1004.1. |
| | |
| | SHT.7-P1-WATER HEATER SHALL BE READILY |
| | ACCESSIBLE PER SPC SEC.501.7.SUPPLY A |
| | FIXED LADDER OR RELOCATE WATER HEATER TO |
| | FLOOR. |
| | |
| | RELIEF DRAIN AND PAN DRAIN SHALL NOT USE |
| | COMMON RISER PER COUNTYWIDE AMENDMENT TO |
| | SPC SEC.507.8.3.,507.8.4. |
| | |
| | SHT.7P-2-NOTE #3-FLOOR SINK OR FLOOR |
| | DRAIN SHALL BE INSTALLED IN LIEU OF HUB |
| | DRAIN. |
| | |
| | SHT.7P-2-NOTE#6-BACKWATER VALVE SHALL BE |
| | ACCESSIBLE PER SPC SEC.1112.5. |
| | |
| | SHT.7P-2-DETAIL #6-VENTS THRU ROOF SHALL |
| | NOT INCREASE IN SIZE PER SPC 905.2,918. |
| | SEE 7P-3-DETAIL#4 ALSO. |
| | |
| | SHT.7P-2-DETAILS#3 & #5-WATER SUPPLY |
| | SHALL COMPLY W/SPC SECS.610.4.1.& |
| | 610.4.2. |
| | |
| | SHT.7P-3-WATER CLOSETS AND FIXTURE |
| | BRANCHES NOT PERMITTED ON WET VENT PER |
| | COUNTYWIDE AMENDMENTS TO SPC SEC.911.1.1 |
| | |
| | VENTING SYSTEM SHALL BE SIZED PER SPC |
| | TABLE 920.2.9 SEE AREA AT BACK TO BACK |
| | WATER CLOSETS. |
| | |
| | COMMENTS CONTINUED ON SECOND PLBG.STEP. |