| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1. THE MAXIMUM HEIGHT OF STAIR RISERS IS | | | 7 INCHES. | | | 2. PROVIDE PROTECTED SINGLE MEANS OF | | | EGRESS FROM MEZZANINE IF USED FOR OTHER | | | THAN DEAD STORAGE. | | | 3. FIRE ALARM SYSTEM SHALL BE CLASS"A" | | | OR ADDRESSABLE. | | | 4. FIRE HYDRANT SHALL BE WITHIN 150 FEET | | | OF FIRE DEPARTMENT CONNECTION. | | | 5. PROVIDE PERMIT AND SHOP DRAWINGS FOR | | | FIRE SPRINKLER AND FIRE ALARM SYSTEMS. |
|