Plan Review Notes
Plan Review Notes For Permit 99120128
Permit Number 99120128
Review Stop R
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00****************UNSAT*******************
 TRUSS SHOP DRAWINGS
 1)ENGINEERED TRUSS PLANS NEED TO BE
 SIGNED,SEALED AND DATED
  
 2)ENGINEERED TRUSS PLAN LAYOUT DOES NOT
 CORRESPOND WITH ARCHITECTURAL TRUSS
 DRAWINGS.SUBMIT REVISED DRAWINGS.
  
 3)SPECIFY CONNECTORS TO BE USED FOR T31,
 T30,T32,GTX,GT1,MGT1,HHGT1,FGT4,T17
 AND ALL OTHERS NOT SHOWN ON SHEET A-7
 OF ARCHITECTURAL PLANS.
  
 4)SHOP DRAWINGS INCORRECTLY REFER TO
 1997 SBCCI DESIGN; CORRECT DESIGN
 STANDARD IS 1997 SBC (STANDARD
 BUILDING CODE)