| Plan Review Notes For Permit 99120128 |
| Permit Number |
99120128 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: STILL NEED TO SUBMIT THE AIC | | | RATINGS FOR EQUIPMENT MAINS!!! | | | MUST BE RATED FOR THE AVAILABLE FAULT | | | CURRENT SET FORTH BY FPL. PER 110-9/110- | | | -10 OF THE NEC. | | | | | | ALSO PLEASE LALEL ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS BEING GFI/GFI | | | PROTECTED. PER 210-8-A-6 | | | | | | NEED TO SUBMIT ALL THE ABOVE INFORMAITON | | | FOR REVIEW AND APPROVAL. IF THERE ARE | | | ANY QUESTION PLEASE CALL. 659-8096 X8372 |
|