| Plan Review Notes For Permit 99120128 |
| Permit Number |
99120128 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | LOCATION OF PLBG.FIXTURES ON SANITARY | | | RISER SHALL MATCH FLOOR PLAN PER COUNTY | | | WIDE AMENDMENTS TO SPC SEC.104.2.1. | | | | | | WATER CLOSETS AND FIXTURE BRANCHES NOT | | | PERMITTED ON WET VENTS PER COUNTYWIDE | | | AMENDMENTS TO SPC SEC.911.1.1 | | | | | | FIXTURES DOWNSTREAM OF WATER CLOSETS | | | SHALL BE VENTED PER SPC SEC.913.2. |
|