| Plan Review Notes For Permit 99120128 |
| Permit Number |
99120128 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************UNSAT******************* | | | | | | 1)NOTE:PLEASE SUBMIT AIC RATING OF ALL | | | EQUIPMENT MAINS AND BRKRS. AIC RATING IS | | | FIGURED FROM FAULT CURRENT CALCULATIONS. | | | REQ`D PER 230-65/110-9/215-5 | | | | | | 2)NOTE: AS REQ`D BY 210-52E WP GFI REC. | | | ARE TO BE INSTALLED FRONT AND BACK OF | | | ALL DWELLING UNITS. | | | | | | 3)NOTE:REQ`D AS PER 210-63 WP GFI REC. | | | FOR ALL A/C EQUIPMENT. | | | | | | 4)NOTE:PLEASE LIST ON PANEL SCHEDULES | | | CIRCUT(S) REQ`D FOR BATH(S) AS PER | | | 210-52D /215-5 | | | | | | 5)NOTE:AS REQ`D BY 250-81 AND 215-5 | | | PLEASE SHOW GROUNDING ELECTRODE CONDUCT- | | | -OR GOING TO BLDG. STEEL ALSO. | | | | | | 6)NOTE: NEED TO SHOW HOW THE GENERATOR | | | CONNECTS WITH THE RISER/PANELS ?????? | | | TRANSFER SWITCH? DISCS? ETC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL. IF THERE ARE | | | ANY QUESTIONS CALL 659-8096 EXT 8372 |
|