Plan Review Notes
Plan Review Notes For Permit 99120128
Permit Number 99120128
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************UNSAT*******************
  
 1)NOTE:PLEASE SUBMIT AIC RATING OF ALL
 EQUIPMENT MAINS AND BRKRS. AIC RATING IS
 FIGURED FROM FAULT CURRENT CALCULATIONS.
 REQ`D PER 230-65/110-9/215-5
  
 2)NOTE: AS REQ`D BY 210-52E WP GFI REC.
 ARE TO BE INSTALLED FRONT AND BACK OF
 ALL DWELLING UNITS.
  
 3)NOTE:REQ`D AS PER 210-63 WP GFI REC.
 FOR ALL A/C EQUIPMENT.
  
 4)NOTE:PLEASE LIST ON PANEL SCHEDULES
 CIRCUT(S) REQ`D FOR BATH(S) AS PER
 210-52D /215-5
  
 5)NOTE:AS REQ`D BY 250-81 AND 215-5
 PLEASE SHOW GROUNDING ELECTRODE CONDUCT-
 -OR GOING TO BLDG. STEEL ALSO.
  
 6)NOTE: NEED TO SHOW HOW THE GENERATOR
 CONNECTS WITH THE RISER/PANELS ??????
 TRANSFER SWITCH? DISCS? ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. IF THERE ARE
 ANY QUESTIONS CALL 659-8096 EXT 8372