Plan Review Notes
Plan Review Notes For Permit 99120126
Permit Number 99120126
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00LOCATION OF FIXTURES ON SANITARY RISER
 SHALL MATCH FLOOR PLAN PER CITY OF WPB
 AMENDMENTS TO SPC SEC.104.2.1.
  
 TUB ,SHOWER AND BIDET NOT PROPERLY
 VENTED.SPC SEC.901.2.
  
 MAIN VENT THRU ROOF REQD.PER SPC SEC.
 904.3.