Plan Review Notes
Plan Review Notes For Permit 99120126
Permit Number 99120126
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************UNSAT***********************
  
 1)NOTE:AS PER 250-81/215-5 NEED TO SHOW
 BLDG.STEEL AS PART OF THE GROUNDING
 ELECTRODE SYSTEM.ALSO GOING TO METERCAN.
  
 2)NOTE: AS PER 210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED. PLEASE SHOW.
  
 3)NOTE: AS PER 1993/1996 NFPA-72 CHAPTER
 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 OF NEW DWELLINGS.
  
 4)NOTE: PLEASE SHOW ON PANEL SCHEDULE
 DEDICATED CIRCUT(S) FOR BATH(S) REQ`D BY
 210-52D ALSO LABEL ALL BATH RECEPTS.GFI
  
 5)NOTE:MISSING WP GFI RECEPTS REQ`DFOR
 A/C COND. UNITS AS PER 210-63
  
 6)NOTE:MISSING GFI RECEPT REQ`D FOR
 GARAGE AS PER 210-52G
  
 7)NOTE:MISSING RECEPTS FOR FRONT AND
 BACK OF DWELLING.AS PER 210-52E
  
 8)NOTE:PLEASE SUBMIT AIC RATING OF ALL
 EQUIPMENT,MAINS AND BRKRS. AIC RATING IS
 FIGURED FROM FAULT CURRENT CALCULATIONS.
 REQ` PER 110-9/215-5.
  
 9)NOTE: PLEASE CORRECT PANEL SHOWING
 AMPS INSTEAD OF VOLTS. 215-5
  
 10)NOTE:LOAD ON PANEL 'B' IS TO INCLUDE
 LOAD OF PANEL 'C'.ALSO 40% OF LOAD ON
 PANEL 'C' IS NOT 361WATTS. PLEASE MAKE
 CHANGE. PLEASE REFIGURE LOAD CALCULATION
 -S ON PANEL'A', 'B',AND 'C',
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND APPROVAL. IF YOU HAVE ANY
 QUESTIONS PLEASE CALL AT 659-8096
 EXT 8372