| Plan Review Notes For Permit 99120124 |
| Permit Number |
99120124 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *******PROVISO**************** | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF ALL | | | EQUIPMENT , MAIN DISC`S AND BRANCH BRKRS | | | AIC RATING IS FIGURED FROM FAULT CURRENT | | | CALCULATUIONS. REQ`D AS PER 110-9/215-5 | | | | | | 2) NOTE:AS PER 250-81/215-5 NEED TO SHOW | | | COMPLETE GROUNDING ELECTRODE SYSTEM. | | | TO INCLUDE BLDG.STEEL | | | | | | 3)NOTE:NO EQUIPMENT GROUNDING CONDUCTOR | | | BWTWEEN METER AND FIRST MEANS OF DISC. | | | | | | 4)NOTE:AS PER 210-52D/215-5 PLEASE LIST | | | DEDICATED BATH(S) CIRCUT ON PANEL | | | SCHEDULE. MUST BE 20AMP #12 AWG. | | | | | | 5)NOTE: AS PER 1993/1996 NFPA-72 | | | 2-2-.1.1.1 SMOKE DETECTORS ARE REQ`D | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS | | | AND ROOMS ABLE TO CONVERT TO SLEEPING | | | ROOMS.W/CLOSET SPACE. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL BEFORE FIRST | | | ROUGH ELECTRICAL INSPECTION IS CALLED IN | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | 659-8096 EXT.8372 |
|