Plan Review Notes
Plan Review Notes For Permit 99120124
Permit Number 99120124
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*******PROVISO****************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF ALL
 EQUIPMENT , MAIN DISC`S AND BRANCH BRKRS
 AIC RATING IS FIGURED FROM FAULT CURRENT
 CALCULATUIONS. REQ`D AS PER 110-9/215-5
  
 2) NOTE:AS PER 250-81/215-5 NEED TO SHOW
 COMPLETE GROUNDING ELECTRODE SYSTEM.
 TO INCLUDE BLDG.STEEL
  
 3)NOTE:NO EQUIPMENT GROUNDING CONDUCTOR
 BWTWEEN METER AND FIRST MEANS OF DISC.
  
 4)NOTE:AS PER 210-52D/215-5 PLEASE LIST
 DEDICATED BATH(S) CIRCUT ON PANEL
 SCHEDULE. MUST BE 20AMP #12 AWG.
  
 5)NOTE: AS PER 1993/1996 NFPA-72
 2-2-.1.1.1 SMOKE DETECTORS ARE REQ`D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 AND ROOMS ABLE TO CONVERT TO SLEEPING
 ROOMS.W/CLOSET SPACE.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL BEFORE FIRST
 ROUGH ELECTRICAL INSPECTION IS CALLED IN
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT.8372