2001-01-08 00:00:00************* PROVISO ****************
  
 1)NOTE: NOW THAT NEW SERVICE IS BEING
 INSTALLED. PLEASE SUBMIT NEW RISER
 DIAGRAM SHOWING SERVICE. TO INCLUDE ALL
 OF THE FOLLOWING: METER, MAIN DISC/MCB.
 ALL CONDUIT SIZES, WIRE SIZES FOR FEEDER
 -S, PLANS SHOW MAIN INSIDE AS EXISTING,,
 IS THIS GOING TO REMAIN? ART;215-5
  
 2)NOTE: PLANS/PANEL SCHEDULE SHOWS 20KW
 OF HEAT BEING FIGURED INTO THE LOAD.???
 PANEL SCHEDULE ONLY SHOW ONE(1) A/C COMP
 AND AIR HANDLER?? IF THERE IS GOING TO
 BE TWO A/C UNITS THEN THEY BOTH NEED TO
 BE ON PANEL SCHEDULE. REQ`D BY NEC ART;
 215-5
  
 3)NOTE:PLEASE LIST THE REQD` DEDICATED
 CIRCUT(S) FOR BATH(S) ON PANEL SCHEDULE.
 AS REQ`D BY 210-52D/ 215-5
  
 4)NOTE: PLEASE CHECK ALL WIRE SIZES FOR
 OVER CURRENT PROTECTION,,,
 A/C COMP AT 2P50 AND HAS #10 AWG,#8 FOR
 AHU MAY NOT BE PROTECTED AT 60 AMPS,THE
 WIRE AMPACITIES MAY ONLY BE USED FROM
 THE 75 DEGREE COLUMN IN ART;310-16
 THE OTHER LOADS FOR POOL PUMP AND HOT
 TUB ARE MOTOR LOADS BUT NAMEPLATE RATING
 SHOULD BE CHECKED FOR MAX. OVERCURRENT
 PROTECTION.
  
 PLEASE HAVE THE ABOVE INFORMATION
 SUBMITTED FOR REVIEW AND APPROVAL BEFORE
 FIRST ROGH ELECTRICALINSPECTION IS
 CALLED IN. IF THERE ARE ANY QUESTIONS
 PLEASE CALL; 659-8096 EXT 8372