| Plan Review Notes For Permit 99120110 |
| Permit Number |
99120110 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************UNSAT********************** | | | | | | 1)NOTE:AS PER 210-52 MISSING OUTLET | | | REQ`D IN BEDROOM #1. | | | | | | 2)NOTE:AS PER ART;210-63 NEED TO HAVE | | | OUTLET FOR A/C COND. UNIT. | | | | | | 3)NOTE:AS PER NFPA-72 2-2.1.1.1 SMOKE | | | DETECTORS ARE REQ`D INSIDE AND OUTSIDE | | | ALL SLEEPING ROOMS OF NEW DWELLINGS. | | | | | | 4)NOTE:AS PER 210-52D BATH GFI NEEDS | | | TO BE ON SEPARATE 20AMP #12 AWG CIRCUT. | | | | | | 5)NOTE: AS REQ`D BY 220-3-D-1 NEED TO | | | SUBMIT LOAD CALCULATION AND SHOW SIZE OF | | | EXISTING SERVICE. PANEL SCHEDULE IS ALSO | | | REQ`D SHOWING EXISTING AND NEW .215-5 | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW AND | | | APPROVAL. IF THERE ARE ANY QUESTIONS | | | CALL 659-8096 EXT 8372,. |
|