Plan Review Notes For Permit 99120110
Permit Number 99120110
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************UNSAT**********************
  
 1)NOTE:AS PER 210-52 MISSING OUTLET
 REQ`D IN BEDROOM #1.
  
 2)NOTE:AS PER ART;210-63 NEED TO HAVE
 OUTLET FOR A/C COND. UNIT.
  
 3)NOTE:AS PER NFPA-72 2-2.1.1.1 SMOKE
 DETECTORS ARE REQ`D INSIDE AND OUTSIDE
 ALL SLEEPING ROOMS OF NEW DWELLINGS.
  
 4)NOTE:AS PER 210-52D BATH GFI NEEDS
 TO BE ON SEPARATE 20AMP #12 AWG CIRCUT.
  
 5)NOTE: AS REQ`D BY 220-3-D-1 NEED TO
 SUBMIT LOAD CALCULATION AND SHOW SIZE OF
 EXISTING SERVICE. PANEL SCHEDULE IS ALSO
 REQ`D SHOWING EXISTING AND NEW .215-5
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW AND
 APPROVAL. IF THERE ARE ANY QUESTIONS
 CALL 659-8096 EXT 8372,.