2001-01-08 00:00:00PROVIDE MANUAL CALCULATIONS WITH THE
 ENERGY CALCULATIONS.
  
 CLARIFY THE DIMENSIONS OF THE EXISTING
 FOOTERS WHICH ARE TO BE REUSED. THEY
 WILL BE REQUIRED TO COMPLY WITH SECT.
 211.6 SBC 1997 CITY WPB AMEND AND BE 4"
 ABOVE GRADE.
  
 THE CODE EDITION REFERENCED ON PLAN A4
 USED FOR THE WIND ANALYSIS IS IN VALID.
 NOTE WE ARE CURRENTLY USING THE 1997
 SBC WITH THE CWPB AMENDMENTS. RECALCULAT
 THE WIND LOADS AND RESUBMIT FOR REVIEW.
 SECT. 16 SBC 1997
  
 SPECIFY THE WIND LOADS FOR THE OVERHEAD
 GARAGE DOOR.PROVIDE PRODUCT APPROVAL
 WHICH SPECIFYS THE DOORS DESIGNED LOADS.
 SECT 16 SBC 1997.
  
 THE PRODUCT APPROVAL SUBMITTED FOR THE
 WINDOWS DOES NOT MEET THE REQUIREMENTS
 OF SECT 1707.4.1 CWPB AMEND.PRODUCTS
 ARE REQUIRED TO BE CERTIFIED BY A
 RECONIZED CERTIFICATION PROGRAM. AT THIS
 TIME THESE PROGRAMS ARE METRO-DADE OR
 SBCCI.
  
 PLANS NEED PALM BEACH COUNTY IMPACT FEE
 REVIEW.