| 2001-01-08 00:00:00 | PROVIDE MANUAL CALCULATIONS WITH THE | | | ENERGY CALCULATIONS. | | | | | | CLARIFY THE DIMENSIONS OF THE EXISTING | | | FOOTERS WHICH ARE TO BE REUSED. THEY | | | WILL BE REQUIRED TO COMPLY WITH SECT. | | | 211.6 SBC 1997 CITY WPB AMEND AND BE 4" | | | ABOVE GRADE. | | | | | | THE CODE EDITION REFERENCED ON PLAN A4 | | | USED FOR THE WIND ANALYSIS IS IN VALID. | | | NOTE WE ARE CURRENTLY USING THE 1997 | | | SBC WITH THE CWPB AMENDMENTS. RECALCULAT | | | THE WIND LOADS AND RESUBMIT FOR REVIEW. | | | SECT. 16 SBC 1997 | | | | | | SPECIFY THE WIND LOADS FOR THE OVERHEAD | | | GARAGE DOOR.PROVIDE PRODUCT APPROVAL | | | WHICH SPECIFYS THE DOORS DESIGNED LOADS. | | | SECT 16 SBC 1997. | | | | | | THE PRODUCT APPROVAL SUBMITTED FOR THE | | | WINDOWS DOES NOT MEET THE REQUIREMENTS | | | OF SECT 1707.4.1 CWPB AMEND.PRODUCTS | | | ARE REQUIRED TO BE CERTIFIED BY A | | | RECONIZED CERTIFICATION PROGRAM. AT THIS | | | TIME THESE PROGRAMS ARE METRO-DADE OR | | | SBCCI. | | | | | | PLANS NEED PALM BEACH COUNTY IMPACT FEE | | | REVIEW. |
|