2001-01-08 00:00:00**************PROVISO*****************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT, MAINS AND BRKRS. AIC RATING
 IOS FIGURED FROM FAULT CURRENT
 CALCULATIONS. AS PER 110-9/215-5
  
 2)NOTE: SUBMIT REVISED RISER DIAGRAM
 TO INCLUDE SIZE OF WIRE ,CONDUITS.ALSO
 PLEASE INDICATE ON PANEL MCB.
  
 3)NOTE: SUBMIT RISER DIAGRAM SHOWING
 COMPLETE GROUNDING SYSTEM AS PER THE
 NEC 250-81/215-5 SHOW GROUND RODS,
 COLD WATER PIPE AND IF ANY BLDG.STEEL
 BEING BONDED.
  
 4)NOTE: AS PER 210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPPACE ARE TO BE
 GFI/GFI PPROTECTED. PLEASE SHOW ALL OUT-
 -LETS AS GFI.
  
 5)NOTE: AS PER 210-52D PLEASE SHOW REQ`D
 DEDICATED CIRCUT FOR BATH(S) AND SHOW
 ON PANEL SCHEDULE. TO BE 20AMP AND #12
 AWG.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL BEFORE FIRTST
 ROUGH ELECTRICAL INSPECTION IS CALLED IN
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372.