| Plan Review Notes For Permit 99111482 |
| Permit Number |
99111482 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************PROVISO***************** | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF | | | EQUIPMENT, MAINS AND BRKRS. AIC RATING | | | IOS FIGURED FROM FAULT CURRENT | | | CALCULATIONS. AS PER 110-9/215-5 | | | | | | 2)NOTE: SUBMIT REVISED RISER DIAGRAM | | | TO INCLUDE SIZE OF WIRE ,CONDUITS.ALSO | | | PLEASE INDICATE ON PANEL MCB. | | | | | | 3)NOTE: SUBMIT RISER DIAGRAM SHOWING | | | COMPLETE GROUNDING SYSTEM AS PER THE | | | NEC 250-81/215-5 SHOW GROUND RODS, | | | COLD WATER PIPE AND IF ANY BLDG.STEEL | | | BEING BONDED. | | | | | | 4)NOTE: AS PER 210-8-A-6 ALL OUTLETS | | | SERVING KITCHEN COUNTERSPPACE ARE TO BE | | | GFI/GFI PPROTECTED. PLEASE SHOW ALL OUT- | | | -LETS AS GFI. | | | | | | 5)NOTE: AS PER 210-52D PLEASE SHOW REQ`D | | | DEDICATED CIRCUT FOR BATH(S) AND SHOW | | | ON PANEL SCHEDULE. TO BE 20AMP AND #12 | | | AWG. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL BEFORE FIRTST | | | ROUGH ELECTRICAL INSPECTION IS CALLED IN | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | 659-8096 EXT 8372. |
|