| Plan Review Notes For Permit 99111444 |
| Permit Number |
99111444 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ******************* | | | | | | NOTES ALREADY GIVEN ON THE SAME THINGS. | | | | | | 1)NOTE:NEED TO SUBMIT THE AIC RATING OF | | | THE EQUIPMENT MAINS!! MAINS ARE TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | AS REQ`D BY 110-9/110-10 OF THE NEC. | | | AIC RATINGS CAN BE FIGURED FROM FAULT | | | CURRENT CALCULATIONS. | | | | | | 2)NOTE:OUTLETS IN KITCHEN ARE STILL NOT | | | SHOWN AS REQ`D BY 210-52. | | | EVERY 2` OF WALL SPACE 6` FROM DOOR ETC. | | | | | | 3)NOTE: PLEASE CHECK PANEL SCHEDULE FOR | | | WIRE SIZES TO MATCH OVERCURRENT | | | PROTECTION.!!! | | | | | | PLEASE HAVE ALL THE ABOVE INFORMATION | | | SUBMITTED FOR REVIEW AND APPROVAL. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | 659-8096 EXT 8372 |
|