Plan Review Notes
Plan Review Notes For Permit 99111444
Permit Number 99111444
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************UNSAT *******************
  
 1)NOTE:ALL OUTLET SPACING IN KITCHEN IS
 TO BE PER ART.210-52 1,2,3,4,5.
  
 2)NOTE:AS PER 210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
  
 3)NOTE:PLEASE DRAW ON ELEC. PLANS A/C
 COND. UNIT SHOWING REQ`D DISC. AND REC.
 AS PER 440-11,210-63 AND 215-5.
  
 4)NOTE:AS PER 210-52G GFI OUTLET IS REQ`
 IN GARAGE.
  
 5)NOTE:SHOW DISC. FOR A/C AIR HANDLER
 UNIT.
  
 6)NOTE: PLEASE SHOW GFI OUTLETS REQ`D
 PER 210-52E FROUNT AND BACK OF RES.
  
 7)NOTE: AS PER 1993/1996 NFPA-72
 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 IN NEW RESIDENTIAL DWELLINGS.
  
 8)NOTE:PLEASE INDICATE ON PANEL WHEATHER
 IT IS MAIN CIRCUT BRKR OR NOT. 215-5
  
 9)NOTE:NEED AIC RATING OF EQUIPMENT /
 MAINS AND BRKRS. AS PER 110-9/215-5
 AIC RATING IS FIGURED FROM FAULT CURRENT
 CALCULATIONS.
  
 10)NOTE: IF DRYER IS 4 KW THEN WHY IS
 BEING PROTECTED WITH 50 AMP BRKR.??
 MOST DRYERS ARE 5KW AND AHVE #10 WIRE
 WITH 30 AMP OVERCURRENT PROTECTION. 50A
 BRKR. IS TOO HIGH FOR 4 KW.
  
 11)PLEASE INCLUDE FRIG.IN LOAD CALC.
  
 12)NOTE:SMALL APPLIANCE CIRCUT(S) SHOW
 #14 AWG. NEEDS TO BE #12 AWG.
  
 13)NOTE:ALSO AS PER 310-16 # 14 ON
 LAUNDRY CIRCUT IS NOT LARGE ENOUGH.NEED
 TO CHANGE TO #12 AWG.
  
 14)NOTE:GEN. LIGHTING SHOW # 14 BEING
 PROTECTED WITH 20AMP BRKR. PLEASE MAKE
 CORRECTION.
  
 15)NOTE:PLEASE SHOW REQ`D DEDICATED
 CIRCUT FOR BATH(S) AS PER 210-52D.CIRCUT
 IS TO BE 20 AMP WITH # 12 WIRE.
  
 16)NOTE: AS PER 250-81/215-5 NEED TO
 SHOW BLDG.STEEL AND COLD WATER PIPE AS
 PART FO THE GROUNDING ELECTRODE SYSTEM.
 YOU SHOW 4/0 AS GROUND CONDUCTOR?? IS
 THIS CORRECT?/ CHECK 250-94 FOR SIZING
 GROUNDING ELECTRODE CONDUCTORS.
  
 17)NOTE: AS PER 215-5 NEED TO CORRELATE
 WIRE SIZES SHOWN!! RISER SHOWS 2-#4`S
 W/ 1-2/0 ?? YET BETWEEN METER AND PANEL
 YOU SHOW 3 1/0 `S?? PLEASE INDICATE WIRE
 BEING USED.
  
 PLEASE RESUBMIT THE ABOVE FOR REVIEW AND
 APPROVAL. IF THERE ARE ANY QUESTION
 PLEASE CALL:659-8096 EXT 8372