| Plan Review Notes For Permit 99111357 |
| Permit Number |
99111357 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | A DRINKING FOUNTAIN IS REQD.ON THE 2ND. | | | FLR.AND IS REQD.TO BE ACCESSIBLE PER SPC | | | TABLE 407 AND FACBC SEC.4.1.3.(10)(A). | | | | | | SQ.FOOTAGE AND OCCUPANT LOAD SHALL BE | | | SHOWN ON THE PLAN PER SPC 407.1.3 AND | | | COUNTYWIDE AMENDMENTS TO SPC.104.2.1. | | | | | | DELETE "STAFF TOILET" LABEL FROM TOILET | | | ROOM FOR COMPLIANCE TO TABLE 407 OF SPC. | | | | | | MOUNTING HEIGHT OF TP DISPENSER REQD.PER | | | FACBC SEC.4.16.6,FIGURE 29(B). | | | | | | WATER SUPPLY CONTROL SHALL COMPLY W/SPC | | | 610.4.2. | | | | | | SINK FOR 2ND FLR NOT SHOWN ON WATER | | | RISER.CLARIFY. |
|