Plan Review Notes
Plan Review Notes For Permit 99111357
Permit Number 99111357
Review Stop B
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00THE FOLLOWING DOORS NEED TO COMPLY WITH
 SECTION 4.13.6 OF THE FLORIDA ACCESS CDE
 HANDICAPP TOLIET B AND A, LOUNGE RM DR 2
 AND EXAM RM#1.
  
 HANDICAPP TOILET B IS REQUIRED TO HAVE
 A 60" CLEARANCE ON THE PULL SIDE.
 SECT 4.13.6 FL ACCESS CODE.
  
 SPECIFY THE REQUIRED CLEARANCES FOR THE
 FIXTURES LOCATED IN THE HANDICAPP TOILET
 SECT 4.19, 4.22, 4.16 FL ACCESS CODE
  
 THE DOOR HARDWARE FOR DOORS NUMBERS 1,3
 DOES NOT COMPLY WITH THE REQUIREMENTS OF
 SECTION 4.13 FLORIDA ACCESS CODE.
  
  
 PROVIDE CONSTRUCTION DETAILS ILLUSTRATIN
 INSTALLING THE EXTERIOR GLASS BLOCK
 AS SPECIFIED IN SECT 2112 STANDARD BUILD
 CODE.
  
 PROVIDE PRODUCT APPROVAL FOR THE NEW
 STOREFRONT. NOTE THIS OPENING WILL
 REQUIRE HURRICANE MISSLE IMPACT PROTECT.
 THE DESIGNER OF RECORD NEEDS TO SPECIFY
 THE WIND PRESURES FOR THIS OPENING.
  
 ENTRY RAMP, THE LANDING ON THE PULL SIDE
 OF THE DOORS NEEDS TO BE 60" DEEP AS
 PER FIGURE 25 FL ACC CODE.
  
 PROVIDE CONSTRUCTION DETAILS FOR THE
 ENTRY RAMP AND RAILING. SECT. 4.7 FL
 ACCESS CODE
  
 NOTE:PLANS APPROVED BY H.PISKURA.STATUS
 IN COMPUTER CHANGED BY T.LARGE IN ORDER
 TO PRINT PERMIT.1/28/00.