| Plan Review Notes For Permit 99111319 |
| Permit Number |
99111319 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | | 1-STORM PANELS: | | | -PROVIDE A COMPLETE INSTALLATION | | | SCHEDULE AS PER CITY SAMPLE. | | | -REVISE DESIGN PRESSURES HIGHLIGHTED ON | | | SHEET 3 OF 5. SEE SHEET 5 OF 5 FOR | | | CORRECT DESIGN PRESSURES. | | | -SHEET 4 OF 5: HIGHLIGHT SPECIFIC | | | CONNECTORS TO BE USED ACCORDING TO THE | | | MOUNTING CONDITIONS, DESIGN PRESSURES, | | | EDGE DISTANCE AND CONNECTION TYPE. | | | 2-PROVIDE PRODUCT APPROVAL FOR: ENTRY | | | DOORS (WITH LEGIBLE DRAWINGS), ARCHED | | | WINDOWS, SLIDING GLASS DOORS WITH | | | TRANSOM ABOVE ASSEMBLY. | | | 3-UPDATE DESIGN CERTIFICATION FOR BLDG | | | CODE COMPLIANCE FORM. | | | 4-TRUSS DRAWINGS: | | | -ENGINEER TO SIGN AND SEAL LAYOUT ALSO. | | | -PROVIDE UPDATED TRUSS DRAWINGS USING | | | SBC 1997 (NOT SBC 1991 OR SBC 1994) OR | | | ASCE 7-95. | | | -DESIGNER OF RECORD TO REVIEW ALL TRUSS | | | DRAWINGS PRIOR TO SUBMITTAL. |
|