Plan Review Notes
Plan Review Notes For Permit 99111317
Permit Number 99111317
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-ENTRY EGRESS DOOR TO HAVE 32" MIN.
 CLEAR OPENING. TABLE 1004 SBC 1997.
 2-PROVIDE PRODUCT APPROVAL FOR: ENTRY
 DOORS WITH TRANSOM ABOVE ASSEMBLY,
 SLIDING GLASS DOORS WITH TRANSOM ABOVE
 ASSEMBLY. (NOTE: SLIDING GLASS DOORS
 TO BE THE REINFORCED TYPE, IN ORDER TO
 MEET THE DESIGN PRESSURES CALCULATED
 BY THE ARCHITECT.
 3-UPDATE THE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM.
 4-TRUSS DRAWINGS:
 -PROVIDE UPDATED ENGINEERED TRUSS
 DRAWINGS USING SBC 1997 ONLY (NOT SBC
 1991 OR 1994) OR ASCE-7-95.
 -DESIGNER OF RECORD TO REVIEW ALL TRUSS
 DRAWINGS PRIOR TO SUBMITTAL.
 5-STORM PANELS:
 -PROVIDE A COMPLETE INSTALLATION
 SCHEDULE AS PER CITY SAMPLE.
 -STORM PANEL DRAWINGS DON'T MATCH
 PRODUCT APPROVAL NUMBER.
 6-CHECK/CLARIFY IF CANTILEVERED BEAM AT
 BREAKFAST AREA IS SUPPOSE TO CARRY THE
 LOAD OF TRUSS GIRDER AT ENTRY PORCH
 AND THE ROOF TRUSSES ABOVE OR IF ROOF
 TRUSSES ARE RESTING ON THE EXTERIOR
 CMU WALL. SEE ROOF FRAMING PLAN.
 PROVIDE ENGINEERED CALCULATIONS FOR
 STRUCTURAL STABILITY OF CANTILEVERED
 BEAM. SEC 104.2.2 CITY AMENDMENTS TO
 SBC 1997.