Plan Review Notes
Plan Review Notes For Permit 99111317
Permit Number 99111317
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************PROVISO*******************
  
 1)NOTE: NEED TO SUBMIT AIC RATING ON
 ALL PLANS FOR EQUIPMENT MAINS/BRKRS AS
 REQ`D BY 110-9/215-5. AIC RATING IS
 FIGURED FROM FAULT CURRENT CALCULATIONS.
  
 2)NOTE:NEED TO INCLUDE BLDG.STEEL AS
 PART OF THE GROUNDING ELECTRODE SYSTEM.
 AS PER 250-81
  
 3)NOTE:AS REQ`D BY NEC EQUIPMENT GROUND-
 -ING BETWEEN MAIN DISC. AND PANEL. SIZE
 PER 250-95
  
 4)NOTE: AS PER 210-52D/215-5 NEED TO
 SHOW DEDICATED BATH(S) 20AMP CIRCUT ON
 PANEL SCHEDULE.
  
 PLEASE SUBMIT THE ABOVE INFORNMATION
 FOR REVIEW AND APPROVAL BEFORE FIRST
 ROUGH ELECTRICAL INSPECTION IS CALLED IN
 IF THERE ARE ANY QUESTIONS PLEASE CALL;
 659-8096 EXT.8372