| Plan Review Notes For Permit 99111317 |
| Permit Number |
99111317 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************PROVISO******************* | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING ON | | | ALL PLANS FOR EQUIPMENT MAINS/BRKRS AS | | | REQ`D BY 110-9/215-5. AIC RATING IS | | | FIGURED FROM FAULT CURRENT CALCULATIONS. | | | | | | 2)NOTE:NEED TO INCLUDE BLDG.STEEL AS | | | PART OF THE GROUNDING ELECTRODE SYSTEM. | | | AS PER 250-81 | | | | | | 3)NOTE:AS REQ`D BY NEC EQUIPMENT GROUND- | | | -ING BETWEEN MAIN DISC. AND PANEL. SIZE | | | PER 250-95 | | | | | | 4)NOTE: AS PER 210-52D/215-5 NEED TO | | | SHOW DEDICATED BATH(S) 20AMP CIRCUT ON | | | PANEL SCHEDULE. | | | | | | PLEASE SUBMIT THE ABOVE INFORNMATION | | | FOR REVIEW AND APPROVAL BEFORE FIRST | | | ROUGH ELECTRICAL INSPECTION IS CALLED IN | | | IF THERE ARE ANY QUESTIONS PLEASE CALL; | | | 659-8096 EXT.8372 |
|