Plan Review Notes
Plan Review Notes For Permit 99111246
Permit Number 99111246
Review Stop P
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00BASED ON THE SQUARE FOOTAGE OF THE SPACE
 AND TABLE 407 OF THE STANDARD PLUMBING
 CODE THE OCCUPANT LOAD IS 21 PEOPLE.
 (BASED ON HABITABLE FLOOR SPACE.SEE SPC
 SEC.407.1.3 FOR ALLOWABLE DEDUCTION OF
 SPECIFIC AREAS AND COMPONENTS).THE MIN.
 REQD.NUMBER OF SANITARY FACILITIES SHALL
 BE:MALES-1 WATER CLOSET,1-LAVATORY.
 FEMALES-2 WATER CLOSETS,2-LAVATORIES.
 DRINKING FOUNTAIN-1.
 SUBMIT CALCULATIONS SHOWING SQUARE FOOT-
 AGE OF ALLOWED DEDUCTIBLE AREAS AND
 HABITABLE FLOOR SPACE.HABITABLE FLOOR
 SPACE SHALL NOT EXCEED 1300 SQ.FEET TO
 COMPLY W/NOTED OCCUPANT LOAD OF 13
 PERSONS.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7.SUPPLY FIXED LADDER OR
 RELOCATE EWH TO FLOOR.CLEARLY SHOW HOW
 EWH COMPLIES W/THIS CODE SECTION-PLANS
 ARE VAGUE.