| Plan Review Notes For Permit 99111246 |
| Permit Number |
99111246 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | BASED ON THE SQUARE FOOTAGE OF THE SPACE | | | AND TABLE 407 OF THE STANDARD PLUMBING | | | CODE THE OCCUPANT LOAD IS 21 PEOPLE. | | | (BASED ON HABITABLE FLOOR SPACE.SEE SPC | | | SEC.407.1.3 FOR ALLOWABLE DEDUCTION OF | | | SPECIFIC AREAS AND COMPONENTS).THE MIN. | | | REQD.NUMBER OF SANITARY FACILITIES SHALL | | | BE:MALES-1 WATER CLOSET,1-LAVATORY. | | | FEMALES-2 WATER CLOSETS,2-LAVATORIES. | | | DRINKING FOUNTAIN-1. | | | SUBMIT CALCULATIONS SHOWING SQUARE FOOT- | | | AGE OF ALLOWED DEDUCTIBLE AREAS AND | | | HABITABLE FLOOR SPACE.HABITABLE FLOOR | | | SPACE SHALL NOT EXCEED 1300 SQ.FEET TO | | | COMPLY W/NOTED OCCUPANT LOAD OF 13 | | | PERSONS. | | | | | | WATER HEATER SHALL BE READILY ACCESSIBLE | | | PER SPC SEC.501.7.SUPPLY FIXED LADDER OR | | | RELOCATE EWH TO FLOOR.CLEARLY SHOW HOW | | | EWH COMPLIES W/THIS CODE SECTION-PLANS | | | ARE VAGUE. |
|