| Plan Review Notes For Permit 99111227 |
| Permit Number |
99111227 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************PROVISO****************** | | | | | | 1)NOTE:PLEASE SUBMIT AIC RATING OF | | | EQUIPMENT MAINS.AS PER 110-9/215-5 | | | | | | 2)NOTE: PLEASE SHOW ROOF TOP REC REQ`D | | | AS PER 210-63. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW AND APPROVAL BEFORE FIRST ROUGH | | | ELECTRICAL INSPECTION IS CALLED IN. |
|