| Plan Review Notes For Permit 99111215 |
| Permit Number |
99111215 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************PROVISO******************* | | | | | | 1)NOTE:E-1 SHOWS ELECTRICAL PANEL 'A' | | | SHEET E-3 DOES NOT SHOW PANEL SCHEDULE | | | FOR PANEL 'A'. PLEASE SUBMIT!! | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS OF | | | MAINS.230-65/110-9/215-5 | | | | | | 3)NOTE:NEED TO HAVE RATED DISC. FROM | | | GENERATOR ON THE INSIDE OF BLDG.INLINE/ | | | INFRONT OF ATS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW AND APPROVAL BEFORE FIRST ROUGH | | | ELECTRICAL INSPECTION IS CALLED IN. IF | | | THERE ARE ANY QUESTIONS PLEASE CALL | | | 659-8096 EXT 8372 |
|