| Plan Review Notes For Permit 99111208 |
| Permit Number |
99111208 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | BAR SINK AND BATH #3 ARE NOT SHOWN ON | | | THE SANITARY RISER DIAGRAM. COUNTYWIDE | | | AMENDMENTS TO STD.PLBG.CODE SEC.104.2.1. | | | | | | DRY VENTS NOT PERMITTED.STACK MUST BE | | | WASHED BY A FIXTURE.SPC SEC.901.2 | | | | | | FIXTURES LOCATED DOWNSTREAM OF W.C.SHALL | | | BE VENTED.SPC 913.2 | | | | | | ONLY 2 WATER CLOSETS PERMITTED ON 3" | | | BLDG.DRAIN PER SPC SEC.714.1 |
|