| Plan Review Notes For Permit 99111208 |
| Permit Number |
99111208 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***********PROVISO********************* | | | | | | 1)NOTE: AS PER 110-9/215-5 NEED TO | | | SUBMIT AIC RATING OF EQUIPMENT MAINS. | | | 2)NOTE:INCLUDE GROUNDING ELECTRODE GOING | | | BLG.STEEL AND COLD WATER PIPE. | | | 3)NOTE:AS PER ART;210-52D NEED TO SHOW | | | REQ`D BATH CIRCUT ON PANEL SCHEDULE. | | | 20 AMP,#12 AWG. | | | 4)NOTE:AS PER ART:210-8-A-6 ALL RECEPTS. | | | SERVING KITCHEN COUNTERSPACE ARE TO BE | | | GFI/GFI PROTECTED. | | | 5)NOTE:AS PER 210-52-C-3 NEED TO SHOW | | | REQ`D RECEPTS. FOR PENINSULAR IN KITCHEN | | | 6)NOTE: AS PER 1996 NFPA-72 | | | SMOKE DETECTORS ARE REQ`D INSIDE AND | | | OUTSIDE ALL SLEEEPING ROOMS. | | | 7)NOTE: AS PER ART;210-52E WP GFI REC. | | | ARE REQ`D FRONT AND BACK OF DWELLINGS. | | | | | | PLEASE SUBMIT FOR REVIEW AND APPROVAL | | | BEFORE FIRST ROUGH ELECTRICAL | | | INSPECTION IS CALLED IN. |
|