Plan Review Notes
Plan Review Notes For Permit 99111208
Permit Number 99111208
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***********PROVISO*********************
  
 1)NOTE: AS PER 110-9/215-5 NEED TO
 SUBMIT AIC RATING OF EQUIPMENT MAINS.
 2)NOTE:INCLUDE GROUNDING ELECTRODE GOING
 BLG.STEEL AND COLD WATER PIPE.
 3)NOTE:AS PER ART;210-52D NEED TO SHOW
 REQ`D BATH CIRCUT ON PANEL SCHEDULE.
 20 AMP,#12 AWG.
 4)NOTE:AS PER ART:210-8-A-6 ALL RECEPTS.
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
 5)NOTE:AS PER 210-52-C-3 NEED TO SHOW
 REQ`D RECEPTS. FOR PENINSULAR IN KITCHEN
 6)NOTE: AS PER 1996 NFPA-72
 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE ALL SLEEEPING ROOMS.
 7)NOTE: AS PER ART;210-52E WP GFI REC.
 ARE REQ`D FRONT AND BACK OF DWELLINGS.
  
 PLEASE SUBMIT FOR REVIEW AND APPROVAL
 BEFORE FIRST ROUGH ELECTRICAL
 INSPECTION IS CALLED IN.