| Plan Review Notes For Permit 99111026 |
| Permit Number |
99111026 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ****************PROVISO***************** | | | | | | 1)NOTE:AS PER ARTS;110-9/215-5 NEED TO | | | SUBMIT AIC RATING OF EQUIPMENT MAINS. | | | 2)NOTE:MISSING OUTLET AS PER210-52 | | | 3)NOTE:AS PER 210-8-A-6 ALL OUTLETS | | | SERVING KITCHEN COUNTERSPACE ARE TO BE | | | GFI/GFI PROTECTED. | | | 4)NOTE;ALSO NOTE AS PER ART210-52-C-3 | | | REQ`D OUTLETS FOR KITCHEN COUNTERSPACE. | | | | | | NEED TO SUBMIT THE ABOVE INFORMATION | | | BEFORE ROUGH ELECTRICAL INSPECTION IS | | | CALLED IN!!! | | | | | | NEED TO ALSO SUBMIT A NEW RISER DIAGRAM | | | BEING LARGER AND MORE CLEAR. |
|