Plan Review Notes
Plan Review Notes For Permit 99111026
Permit Number 99111026
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00****************PROVISO*****************
  
 1)NOTE:AS PER ARTS;110-9/215-5 NEED TO
 SUBMIT AIC RATING OF EQUIPMENT MAINS.
 2)NOTE:MISSING OUTLET AS PER210-52
 3)NOTE:AS PER 210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
 4)NOTE;ALSO NOTE AS PER ART210-52-C-3
 REQ`D OUTLETS FOR KITCHEN COUNTERSPACE.
  
 NEED TO SUBMIT THE ABOVE INFORMATION
 BEFORE ROUGH ELECTRICAL INSPECTION IS
 CALLED IN!!!
  
 NEED TO ALSO SUBMIT A NEW RISER DIAGRAM
 BEING LARGER AND MORE CLEAR.