| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************UNSAT********************* | | | | | | 1)NOTE:PLEASE SUBMIT RISER DIAGRAM | | | SHOWING EQUIPMENT,SHOW ALL PANELS,CONDUI | | | SIZES, WIRE SIZES. GROUNDING ELECTRODE | | | SYSTEM TO INCLUDE GROUND ROD BLDG.STEEL | | | AND COLD WATER PIPE IF ANY. | | | SUBMIT AIC RATING OF EQUIPMENT MAINS, | | | BRKRS. AS PER 110-9/215-5. | | | THE RISER DIAGRAM AND PANEL SCHEDULE | | | SHOULD BE DRAWN SEPARATE FROM OTHER | | | ELEC.DRAWINGS. | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW AND | | | APPROVAL. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 561-659-8096 EXT,8372 |
|