| Plan Review Notes For Permit 99110858 |
| Permit Number |
99110858 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | CORRECTED BY REVISIONS****************** | | | | | | 1)1997 SBC 411.5.4 REQUIRES GARAGES TO | | | BE CONTINUOUSLY VENTILATED BY A MECHAN- | | | ICAL SYSTEM WITH A POSITIVE MEANS FOR | | | BOTH INLET AND EXHAUST OF AT LEAST 0.75 | | | CFM PER SQ FT OF FLOOR AREA, 411.4.2 | | | REQUIRES AT LEAST 6 AIR CHANGES PER HOUR | | | F0R EACH LEVEL. PROVIDE CALCULATIONS | | | SHOWING COMPLIANCE. | | | 2) MECHANICAL PLANS SHOW C02 SENSOR, | | | CODE REQUIRES REMOVAL OF PRODUCTS OF | | | COMBUSTION. IS THIS SUPPLIMENTAL TO | | | CONTINUOUS VENTILATION AS REQUIRED ABOVE | | | AND WHAT FUNCTION DOES TIME CLOCK HOLD? | | | 3) ACCESS DOORS REQUIRED FOR FIRE DAMPER | | | ACCESS. PROVIDE DETAILS FOR REQUIRED | | | FIRE DAMPER ACCESS |
|