| Plan Review Notes For Permit 99110632 |
| Permit Number |
99110632 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************UNSAT******************** | | | | | | 1)NOTE:AS REQ`D BY 1993/1996 NFPA-72 | | | 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS | | | IN NEW DWELLINGS. | | | | | | 2)NOTE:AS REQ`D PER 210-52D/215-5 PLEASE | | | INCLUDE BATH(S) DEDICATED GFI CIRCUT(S). | | | LIST ON PANEL SCHEDULE. | | | | | | 3)NOTE:PLEASE SHOW AND INCVLUDE AS PART | | | OF THE GROUNDING ELECTRODE SYSTEM THE | | | GROUND ROD , COLD WATER PIPE AS PER | | | 250-81/215-5. | | | | | | 4)NOTE: NEED TO SUBMIT AIC RATING OF | | | EQUIPMENT MAINS TO INCLUDE BRKRS. AS PER | | | 110-9/215-5 | | | | | | 5)NOTE:AS REQ`D BY 210-52E NEED TO HAVE | | | RECEPT. ON THE FRONT OF DWELLING. | | | | | | 6)NOTE: NEED TO SHOW SEPARATE LOAD CAL- | | | CULATION FOR EACH UNIT. | | | | | | NEED TO SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL.IF THERE ARE ANY | | | QUESTIONS PLEASE CALL 659-8096 EXT8372. |
|